4. Installation
1
2
28
If the installation criteria for good degassing cannot be met, a manual
bleed degasser R must always be installed at the high point(s) of the
solar equipment.
4
A
Z
E
R
3
M001755-A
n Connecting
4 Use of a hacksaw is prohibited.
4 Pipe connections by compression fittings.
4 Hard soldering: Hard soldering: hard soldering filler metal without
flux in accordance with DIN EN 1044, e.g. L-Ag2P or L-CuP6.
4 Pipe fittings: can only be used if they are resistant to glycol,
pressure (6 bar) depending on version) and temperature (-30 °C,
180 °C) (manufacturer's data).
M001756-A
4 Sealing material: Hemp.
4 Press fitting (6 bar, 140 °C).
n Pipe insulation
Ideal
Incorrect (high point with no air vent)
Correct (high point with air vent)
Location of manual bleed valve degasser
CAUTION
Soft soldering is not authorized.
The use of flux promotes corrosion conditions in systems
operating with propylene glycol as heat transfer fluid. In all
cases the inside of the pipes must be flushed.
CAUTION
To protect the insulation against mechanical damage, bird
picking and UV light, add extra protection for the heat
insulation sleeves in the roof area by using an aluminium
sheet sleeve or aluminium adhesive tape. This additional
protection must be sealed with silicone.
200SE-2S - 300SE-2S
26/04/2016 - 7607575-05