Ring Redundancy

3.1.1 Setting up and configuring the HIPER-Ring

Set up the network to meet your requirements.
You configure all 6 ports so that the transmission speed and the duplex
settings of the lines correspond to the following table:
Bit rate
Autonegotiation
(automatic configuration)
Port
Duplex
Table 2: Port settings for ring ports
Select the Redundancy:Ring Redundancy dialog.
Under "Version", select HIPER-Ring.
Define the desired ring ports 1 and 2 by making the corresponding
entries in the module and port fields. If it is not possible to enter a
module, then there is only one module in the device that is taken
over as a default.
Display in "Operation" field:
– active: This port is switched on and has a link.
– inactive: This port is switched off or it has no link.
26
100 Mbit/s
off
on
Full
3.1 Example of HIPER-Ring
1000 Mbit/s
on
on