Setting Up And Configuring The Hiper-Ring - Hirschmann RS20 User Manual

Industrial ethernet switch
Hide thumbs Also See for RS20:
Table of Contents

Advertisement

Ring Redundancy
2.1.1

Setting up and configuring the HIPER-Ring

Set up the network to meet your demands.
You configure all 6 ports so that the transmission speed and the duplex
settings of the lines correspond to the following table:
Bit rate
Autonegotiation
(automatic configuration)
Port
Duplex
Table 3: Port settings for ring ports
Note: When activating the HIPER-Ring function, the device sets the
corresponding settings for the pre-defined ring ports in the configuration table
(transmission rate and mode). If the HIPER-Ring function is switched off, the
ports, which are changed back into normal ports, keep the ring port settings.
Independently of the DIP switch setting, you can still change the port settings
via the software.
Select the Redundancy:Ring Redundancy dialog.
Under "Version", select HIPER-Ring.
Define the desired ring ports 1 and 2 by making the corresponding
entries in the module and port fields. If it is not possible to enter a
module, then there is only one module in the device that is taken
over as a default.
Redundancy L2B
Release 6.0 07/2010
100 Mbit/s
off
on
Full
2.1 Example of a HIPER-Ring
1000 Mbit/s
on
on
17