Ring Redundancy
Note: Configure all the devices of the MRP-Ring individually. Before you
connect the redundant line, you must complete the configuration of all the de-
vices of the MRP-Ring. You thus avoid loops during the configuration phase.
Set up the network to meet your requirements.
You configure all 6 ports so that the transmission speed and the duplex
settings of the lines correspond to the following table:
Bit rate
Autonegotiation
(automatic configuration)
Port
Duplex
Table 3: Port settings for ring ports
Select the Redundancy:Ring Redundancy dialog.
Under "Version", select MRP.
Define the desired ring ports 1 and 2 by making the corresponding
entries in the module and port fields. If it is not possible to enter a
module, then there is only one module in the device that is taken
over as a default.
Display in "Operation" field:
forwarding: this port is switched on and has a link.
blocked: this port is blocked and has a link.
disabled: this port is switched off
not connected: this port has no link.
Redundanz L2P
Release 5.0 04/09
100 Mbit/s
off
on
Full
3.2 Example of MRP-Ring
1000 Mbit/s
on
on
31