Noise Information; Installation Of The Heat Pump; Flexible Hoses; Positioning The Heat Pump - Danfoss DHP-iQ Installation Manual

Table of Contents

Advertisement

Installation Guide
4.5

Noise information

4.5.1

Installation of the heat pump

To prevent disturbing noise from the heat pump the following recommendations should be observed:
▪ In the event the heat pump is positioned on a vibration sensitive base, vibration dampers should be used. The vibration dampers
must be correctly dimensioned with regard to the heat pump's weight so that static spring depression of at least 2 mm is obtained
in all mounting components.
▪ Connection of the heat transfer fluid to the heat pump must be made using a flexible hose to prevent transmission of vibration to
building construction and the pipe system, see Flexible hoses.
▪ Do NOT install expansion vessel on the connection for the bleed valve.
▪ Ensure that pipes at lead-ins are not lying against the walls.
▪ Ensure that the electrical supply cable does not provide a path for vibration because it is overstretched.
▪ In cases where attachment of pipes to sensitive construction elements cannot be avoided, special elastic pipe attachments should
be used.
4.5.2

Flexible hoses

All pipes should be routed in such a way that vibrations cannot be transmitted from the heat pump through the piping and out into the
building. This also applies to the expansion pipe. We recommend that flexible hoses are used for all pipe connections to avoid the trans-
mission of vibrations. Flexible hoses are available to purchase as accessories. The figures below show how appropriate and inappropriate
installations look using this type of hose.
4.6

Positioning the heat pump

Decide the installation location regarding the following condition and obtain the user's approval. The location of the outdoor unit is
chosen so that neither the own living environment or adjoining properties are exposed to noise interference.
▪ The outdoor unit must not be placed on its side or upside down, as the compressor lubrication oil will run into the cooling circuit
and seriously damage the unit.
▪ Choose a location that is dry and sunny, but not exposed to direct sunlight or strong winds.
▪ Do not block any passageways or thoroughfares.
28
DHP-iQ
VIJSS102
Danfoss Heating Solutions

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents