Danfoss DHP-iQ Installation Manual page 43

Table of Contents

Advertisement

Installation Guide
Be sure to install both an earth leakage detector and circuit breaker
N
with specified capacity in accordance with relevant local and national
regulations. -If it is not installed properly, it may cause electric shocks
and fire.
6.1
Fuse table
Outdoor Unit Mains
Supply
230V 1-N, 50Hz
400V 3-N, 50Hz
Tab. 3: Fuse table
Danfoss Heating Solutions
DHP-iQ
Fuse size
5kW
9kW
16kW
16 A
16 A
25 A
-
10 A
16 A
Indoor Unit
DHP-
DHP-iQ Maxi (including immersion heat-
Mains Supply
iQ
Mini
3kW
Fuse
size
230V 1-N,
10 A
16 A
50Hz
400V 3-N,
-
10 A
50Hz
VIJSS102
er) Fuse size
6kW
9kW
12kW
15kW
32 A
50 A
-
-
16 A
16 A
20 A
25 A
43