8-2.

INDOOR UNIT

GENERAL RULES OF DRAIN PROCESS
Install the drain pipe with downward gradient (1/100 or more) and so there are no rises in the
pipe.
Use general hard polyvinyl chloride pipe and connect it with adhesive (polyvinyl chloride) so
that there is no leakage.
Support the drain pipe with supporters each 5 to 7ft. (1.5 to 2.0m)
Do not perfrom air bleeding.
Always heat insulate the indoor side of the drain pipe.
When connecting the drain hose to the indoor unit, use the accessory band. (Except compact
wall mounted type and wall mounted type)
COMPACT CASSETTE TYPE
11-13/16 (300) or less
PVC pipe
(Local
arrangement)
drain hose
(3/4 inch)
(accessory)
Attached band
Rise
Drain lift-up pipe restrictions:
(1) Lift-up height ≤ 27-9/16in. (700mm) (from ceiling)
(2) Drain hose (pipe) length ≤ 11-13/16in. (300mm) (between indoor unit and lift-up pipe)
When a dimensions exceed the above restrictions will cause water leakage.
Unit: in. (mm)
Downward
gradient 1/100
or more
Horizontal or
upward gradient
Not good
Air bleeding
Trap
CAUTION
- (06 - 105) -
5 to 7ft.
(1.5 to 2.0m)
Downward gradient
1/100 or more
6. SYSTEM DESIGN