ADDITIONAL CHARGE CALCULATION
●
The outdoor unit is charged refrigerant at the factory.
●
Additional refrigerant required to be charged on site depending on pipe length.
●
The additional refrigerant charge amount is calculated according to the following formula.
●
Round up the calculated result to two decimal places.
CALCULATION OF ADDITIONAL CHARGE REFRIGERANT
Diameter of liquid
pipe
unit: in. (mm)
ø1/4 (6.35)
ø3/8 (9.52)
Calculation of additional amount for pipe length
Total
length of
x 0.624
ø3/8in.
oz./ft.
(9.52mm)
(58g/m)
liquid pipe
ft (m)
oz. (g)
Additional amount for
pipe length
unit: oz./ft. (g/m)
0.224 (21)
0.624 (58)
Total
length of
x 0.224
ø1/4in.
oz./ft.
(6.35mm)
(21g/m)
liquid pipe
+
=
ft (m)
oz. (g)
- (06 - 17) -
Total
Total
=
oz. (g)
lbs (kg)
6. SYSTEM DESIGN