STOP OPERATION MODE
•
It is possible to switch to Batch stop or Emergency stop and Normal operation by using external
input.
Circuit diagram example
Outdoor unit
control PC board
Connector
1
2
* Make the distance from the PC board to the connected unit within 33ft. (10m).
•
Use the following parts and construct a circuit as shown above.
•
Set the "Batch stop" or "Emergency stop" pattern, refer to "5.FUNCTION SETTING"
●
When function setting is "Batch stop" mode
On
Input signal
Off
Batch stop
Command
Normal
Operation
Air conditioner
Stop
Remote controller
Connected unit
Ex.) Switch
Contact capacity : 24VDC or more, 10mA or more.
*33ft. (10m)
Signal
Field supply
- (06 - 93) -
On
On
Remote control
operation validity
6. SYSTEM DESIGN