Fujitsu AOU48RLXFZ Design & Technical Manual page 247

Hybrid flex inverter system
Table of Contents

Advertisement

STOP OPERATION MODE
It is possible to switch to Batch stop or Emergency stop and Normal operation by using external
input.
Circuit diagram example
Outdoor unit
control PC board
Connector
1
2
* Make the distance from the PC board to the connected unit within 33ft. (10m).
Use the following parts and construct a circuit as shown above.
Set the "Batch stop" or "Emergency stop" pattern, refer to "5.FUNCTION SETTING"
When function setting is "Batch stop" mode
On
Input signal
Off
Batch stop
Command
Normal
Operation
Air conditioner
Stop
Remote controller
Connected unit
Ex.) Switch
Contact capacity : 24VDC or more, 10mA or more.
*33ft. (10m)
Signal
Field supply
- (06 - 93) -
On
On
Remote control
operation validity
6. SYSTEM DESIGN