Fujitsu AOU48RLXFZ Design & Technical Manual page 207

Hybrid flex inverter system
Table of Contents

Advertisement

SETTINGS LIST
LED961
LED962
Setting Mode
CODE No.
CODE No.
0
Cooling
1
1
0
capacity shift
0
0
Switching
between
2
0
batch stop or
emergency stop
0
0
Operation
2
1
mode selecting
method
0
0
2
8
Forbidden
0
0
2
9
Forbidden
0
0
0
Energy saving
3
0
level setting
0
0
0
Low noise
4
1
mode setting
0
0
Low noise
mode
4
2
0
operation level
setting
0
Factory
Setting Function
setting
0
Standard
1
High power mode 1
2
High power mode 2
0
Batch stop
1
Emergency stop
Priority given to the
0
first command
Priority given to
1
external input of
outdoor unit
0
Forbidden
1
Forbidden
0
Forbidden
1
Forbidden
0
Level 1 (stop)
Level 2
1
(Limited at 50%)
Level 3
2
(Limited at 75%)
Level 4
3
(Limited at 100%)
0
Off (Normal)
1
On (Low noise mode)
Level 1
0
(-3dB)
Level 2
1
(-6dB)
Level 3
2
(-9dB)
- (06 - 53) -
Remarks
Use it when becoming cooling capacity
shortage.
Use High power mode 2 when becoming
cooling capacity shortage in High power
mode 1.
This mode selects the pattern of the stop
function to be operated by the external
input terminal (CN934).
•Batch stop: The stop of all indoor units
connected to same refrigerant system due
to input signal coming from CN934.
•Emergency stop: When emergency
stop is actuated, the indoor unit does not
accept the operation command from the
remote controller. On the other hand,
when the emergency stop is released (no
input from CN934), the air conditioner
does not return to the original operation
until operate indoor unit by the remote
controller.
Select the priority setting of the operation
mode.
•Priority given to the first command:
Priority is given to the operation mode
which is set first.
•Priority given to external input of outdoor
unit: Priority is given to the operation
mode which is set by the external input
terminal (CN932).
Setting forbidden
Setting forbidden
The capacity limit can be selected when
operating with the "Energy Saving Peak
Cut function."
The operation selection can be done by
external input terminal(CN933).
The lower the level, the more the effect
of energy saving, but the cooling/heating
performance decreases.
When "Low noise mode ON" is selected,
the operating noise will be suppressed.
Without external input terminal: It operates
by selecting Low noise mode ON.
With external input terminal: The operation
selection can be done by external input
terminal(CN931) by selecting Low noise
mode OFF.
The noise level when operating in the low
noise mode can be set.
Cooling/heating performance decreases
by lowering operation noise level.