4-3.
TRANSMISSION LINE
TRANSMISSION WIRING SPECIFICATIONS
●
Between Outdoor unit to Branch box
●
Between Branch box to Branch box
●
Between Branch box to Indoor unit
●
Between Central remote controller to Branch box
TRANSMISSION WIRING LIMITATION
d
Outdoor unit - Branch box (primary)
Branch box (primary) - Branch box (secondary)
(each unit)
Branch box - Indoor unit
(each unit)
Central remote controller - Branch box
(Total length)
Use
Central remote
controller
a
b
Branch box 1 (primary)
Branch box 2 (secondary)
e
f
g
d, e, f, g, h, i, j, k
- (06 - 43) -
Cable size
14 AWG
22 AWG
l
c
Branch box 3 (secondary)
h
i
j
Maximum length [ft. (m)]
a
246 (75)
b, c
246 (75)
246 (75)
l
1640 (500)
Remarks
208/230V 60Hz
3Wire + ground
Sheathed PVC cable
Polar 3core
k