3-1-2.
MULTIPLE OUTDOOR UNIT INSTALLATION
Provide at least 1inch (25mm) of space between the outdoor units if multiple units are
installed.
When routing the piping from the side of an outdoor unit, provide space for the piping.
No more than 3 units must be installed side by side.
When 3 units or more are arranged in a line, provide the space as shown in the following
example when an obstruction is present also in the upward area.
WHEN THE UPWARD AREA IS OPEN
Obstacles at rear only
11-13/16 (300)
WHEN AN OBSTRUCTION IS PRESENT ALSO IN THE UPWARD
AREA
Obstacles at rear and above only
59-1/16 (1500)
3-1-3.
OUTDOOR UNITS INSTALLATION IN MULTI ROW
Single parallel unit arrangement
78-3/4 (2000) or more
23-5/8 (600)
39-3/8 (1000)
Obstacles at front only
59-1/16 (1500) or more
59-1/16 (1500)
19-11/16 (500)
Max. 11-13/16 (300)
5-29/32 (150)
- (03 - 07) -
Obstacles at front and rear only
59-1/16 (1500) or more
Multiple parallel unit arrangement
19-11/16 (500)
118-1/8 (3000) or more
23-5/8 (600)
59-1/16 (1500)