5-10.

DUCT STATIC PRESSURE SETTING

MODELS : ARU9RLF, ARU12RLF, ARU18RLF, ARU24RLF
The air flow setting other than the default value of 0.1inWG (25 Pa) may be changed to the
required external static pressure.
Setting of the air flow can be changed with the wireless remote controller, wired remote
controller, and simple remote controller.
How to set air flow (external static pressure)
W
ireless remote controller
Air flow is set by function number 26 (static pressure).
Refer to "BUTTON NANE AND FUNCTION", "FUNCTION SETTING" and "FUNCTION
DETAILS" in 5-3 INDOOR UNIT (setting by wireless remote controller).
Wired remote controller
Air flow is set by function number 26 (static pressure).
Refer to "BUTTON NANE AND FUNCTION", "FUNCTION SETTING" and "FUNCTION
DETAILS" in 5-4. INDOOR UNIT (setting by wired remote controller).
Simple remote controller
Air flow is set by function number 26 (static pressure).
Refer to "BUTTON NANE AND FUNCTION", "FUNCTION SETTING" and "FUNCTION
DETAILS" in 5-5 INDOOR UNIT (setting by simple remote controller).
FAN PERFORMANCE CURVE
Refer to Chapter 4. INDOOR UNITS
If air flow setting is unmatched, it is caused to be air flow down or water leakage due to
wrong operation.
Range of static pressure at ARU24 model is different from the others.
Note
- (06 - 80) -