1. Model lineup Indoor unit AUU7RLF ARU7RLF ARU18RLF AUU9RLF ARU9RLF AUU12RLF ARU12RLF AUU18RLF ASU7RLF1 ASU18RLF AGU9RLF ASU9RLF1 AGU12RLF ASU12RLF1 AGU15RLF ASU15RLF1 Outdoor unit AOU18RLXFZH AOU24RLXFZH ¢ Indoor units that can be connected to each outdoor unit ●: Connectable / -: Not connectable...
2. Specifications 2-1. Compact cassette type Model name AUU7RLF AUU9RLF AUU12RLF AUU18RLF Power supply 208/230 V ~ 60 Hz Available voltage range 187—264 V Capacity Btu/h class 7,000 9,000 12,000 18,000 Input power Running current 0.15 0.15 0.19 0.30 HIGH...
2-2. Slim duct type Model name ARU7RLF ARU9RLF ARU12RLF Power supply 208/230 V ~ 60 Hz Available voltage range 187—264 V Capacity Btu/h class 7,000 9,000 12,000 Input power Running current 0.30 0.30 0.35 HIGH 324 (550) 353 (600) 383 (650) 288 (490) 324 (550) 353 (600)
Page 12
Model name ARU18RLF Power supply 208/230 V ~ 60 Hz Available voltage range 187—264 V Capacity Btu/h class 18,000 Input power Running current 0.44 HIGH 554 (940) 518 (880) Cooling 483 (820) QUIET 442 (750) Airflow rate CFM (m HIGH 554 (940) 518 (880) Heating...
2-3. Wall mounted type Model name ASU7RLF1 ASU9RLF1 ASU12RLF1 ASU15RLF1 Power supply 208/230 V ~ 60 Hz Available voltage range 187—264 V Capacity Btu/h class 7,000 9,000 12,000 14,000 Input power Running current 0.13 0.15 0.19 0.25 HIGH 330 (560) 353 (600) 388 (660) 430 (730)
Page 14
Model name ASU18RLF Power supply 208/230 V ~ 60 Hz Available voltage range 187—264 V Capacity Btu/h class 18,000 Input power Running current 0.32 HIGH 542 (920) 436 (740) Cooling 365 (620) QUIET 324 (550) Airflow rate CFM (m HIGH 542 (920) 436 (740) Heating...
2-4. Floor type Model name AGU9RLF AGU12RLF AGU15RLF Power supply 208/230 V ~ 60 Hz Available voltage range 187—264 V Capacity Btu/h class 9,000 12,000 14,000 Input power Running current 0.15 0.18 0.20 HIGH 312 (530) 353 (600) 383 (650) 259 (440) 288 (490) 306 (520)
3. Dimensions 3-1. Compact cassette type ¢ Models: AUU7RLF, AUU9RLF, AUU12RLF, and AUU18RLF Unit: in (mm) • Cassette grille mounting state 20-7/8 (530): Hanging bolt position 5-5/16 9-13/16 (250) (135) op view Be sure to leave Maintenance space maintenance space...
Page 17
95 (2,400) or more Obstruction Floor Maximum height from floor to ceiling [Unit: in (mm)] Model name AUU7RLF and AUU9RLF AUU12RLF and AUU18RLF Standard mode (2,700) High ceiling mode — (3,000) • 3-way direction setting Unit: in (mm)
3-2. Slim duct type ¢ Models: ARU7RLF, ARU9RLF, and ARU12RLF Unit: in (mm) 22-5/8 (574) 2 (51) View A Rear view Drain port 3-15/16 (100) x 6 = 23-5/8 (600) 1-7/8 (47) 25-9/16 (650) 2-3/16 (55) 3-1/16 (78) 28-7/8 (734) 3-1/2 (89) 1-7/8 (48) 4-11/16 (119)
Page 19
¢ Model: ARU18RLF Unit: in (mm) 2 (51) 30-1/2 (774) Rear view View A Drain port 1-7/8 (47) 3-15/16 (100) x 8 = 31-1/2 (800) 2-3/16 (55) 3-1/16 (78) 33-7/16 (850) 3-1/2 (89) 36-3/4 (934) 3-7/16 (87) 4-11/16 (119) Top view 2-3/16 (56) 6-9/16 (167)
Page 20
¢ Installation space requirement Provide sufficient installation space for product safety. In ceiling-concealed installations: Unit: in (mm) 12 (300) or more Strong and durable ceiling 1 (20) or more Indoor unit Left Right side side 1 (20) or more 12 (300) 4 (100) Service access Ceiling...
Page 21
¢ Maintenance space requirement For future maintenance and service access, provide sufficient maintenance space. NOTE: Do not place any wiring or illumination in the maintenance space, as they will impede ser- vice. Unit: in (mm) Service access Unit Control 12 (300) or more Service space - 15 -...
3-3. Wall mounted type ¢ Models: ASU7RLF1, ASU9RLF1, ASU12RLF1, and ASU15RLF1 Unit: in (mm) 33-1/16 (840) 8 (203) (33-1/16 (840)) 13-7/8 (353) 3-1/16 (78) 1-3/4 (45) 14-5/16 (364) Ø2-9/16 (Ø65) Ø2-9/16 (Ø65) for pipe inlet for pipe inlet 3-7/16 4-9/16 12-3/8 (315) 12-5/8 (321) (88)
Page 23
Installation space Unit: in (mm) Outline of unit 1 (25) or more 3 (52) or more 3 (70) 6 (130) or more 60 (1,500) or more or more - 17 - 3-3. Wall mounted type 3. Dimensions...
Page 24
¢ Model: ASU18RLF Unit: in (mm) 39-5/16 (998) 9 (228) Unit center Outline of unit 1-1/8 (28) 2-5/8 (67) 35-9/16 (903) 13/16 (20) 17-1/4 (438) 15-5/8 (397) Ø 3-1/8 (80) hole 39-5/16 (998): Unit size Ø 3-1/8 (80) hole Piping inlet Piping inlet - 18 - 3-3.
Page 25
Installation space Unit: in (mm) Outline of unit 3 (52) or more 3 (53) or more 4 (80) or more 5 (120) or more 60 (1,500) or more - 19 - 3-3. Wall mounted type 3. Dimensions...
3-4. Floor type ¢ Models: AGU9RLF, AGU12RLF, and AGU15RLF Unit: in (mm) 7-7/8 (200) 29-1/8 (740) Side view Front view ¢ Installation space Unit: in (mm) 4 (100) or more 4 (80) or more 4 (80) or more 2 (50) or more 5 (150) or less - 20 -...
5. Air velocity and temperature distributions 5-1. Compact cassette type ¢ Models: AUU7RLF and AUU9RLF • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH (ft) Unit: ft/s (m/s) 1 (0.25) 2 (0.5) 3 (1.0) 7 (2.0) 3 (1.0) 7 (2.0)
Page 33
Measuring conditions Fan speed Operation mode Outlet directions NOTE: Reference data HIGH HEAT 4-way air outlet • Air velocity distribution (ft) Unit: ft/s (m/s) 7 (2.0) 7 (2.0) 5 (1.5) 5 (1.5) 3 (1.0) 3 (1.0) 2 (0.5) 2 (0.5) Side view Vertical airflow direction louver: Down 1 (0.25)
Page 34
¢ Model: AUU12RLF • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH (ft) Unit: ft/s (m/s) 1 (0.25) 2 (0.5) 3 (1.0) 7 (2.0) 7 (2.0) 3 (1.0) 1 (0.25) Top view 2 (0.5) 2 (0.5) Vertical airflow direction louver: Up 1 (0.25) 7 (2.0) 7 (2.0)
Page 35
Measuring conditions Fan speed Operation mode Outlet directions NOTE: Reference data HIGH HEAT 4-way air outlet • Air velocity distribution Unit: ft/s (m/s) (ft) 5 (1.5) 5 (1.5) Side view 3 (1.0) 3 (1.0) Vertical airflow direction louver: Down 2 (0.5) 2 (0.5) 1 (0.25) 1 (0.25)
Page 36
¢ Model: AUU18RLF • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH (ft) Unit: ft/s (m/s) 1 (0.25) 2 (0.5) 3 (1.0) 7 (2.0) 7 (2.0) 1 (0.25) Top view 2 (0.5) 3 (1.0) 3 (1.0) 2 (0.5) Vertical airflow direction louver: Up 1 (0.25) 7 (2.0)
Page 37
Measuring conditions Fan speed Operation mode Outlet directions NOTE: Reference data HIGH HEAT 4-way air outlet • Air velocity distribution Unit: ft/s (m/s) (ft) 7 (2.0) 7 (2.0) 5 (1.5) 5 (1.5) 3 (1.0) 3 (1.0) Side view Vertical airflow direction louver: Down 2 (0.5) 2 (0.5) 1 (0.25)
5-2. Slim duct type ¢ Model: ARU7RLF NOTE: This data is measured after installing optional Auto louver grille kit. Fan speed Operation mode Measuring conditions HIGH • Air velocity distribution (ft) Unit: ft/s (m/s) Top view 7 (2) 3 (1) 2 (0.5) Vertical airflow direction louver: Up Horizontal airflow direction louver: Center...
Page 39
Fan speed Operation mode Measuring conditions HIGH HEAT • Air velocity distribution (ft) Unit: ft/s (m/s) 7 (2) Side view Vertical airflow direction louver: Down 3 (1) Horizontal airflow direction louver: Center 2 (0.5) (ft) • Air temperature distribution (ft) Unit: °F (°C) 86 (30) 82 (28)
Page 40
¢ Model: ARU9RLF NOTE: This data is measured after installing optional Auto louver grille kit. Fan speed Operation mode Measuring conditions HIGH • Air velocity distribution (ft) Unit: ft/s (m/s) Top view 7 (2) 3 (1) 2 (0.5) Vertical airflow direction louver: Up Horizontal airflow direction louver: Center (ft) (ft)
Page 41
Fan speed Operation mode Measuring conditions HIGH HEAT • Air velocity distribution (ft) Unit: ft/s (m/s) 7 (2) Side view Vertical airflow direction louver: Down Horizontal airflow direction louver: Center 3 (1) 2 (0.5) (ft) • Air temperature distribution (ft) Unit: °F (°C) 86 (30) Side view...
Page 42
¢ Model: ARU12RLF NOTE: This data is measured after installing optional Auto louver grille kit. Fan speed Operation mode Measuring conditions HIGH • Air velocity distribution (ft) Unit: ft/s (m/s) Top view 7 (2) 3 (1) 2 (0.5) Vertical airflow direction louver: Up Horizontal airflow direction louver: Center (ft) (ft)
Page 43
Fan speed Operation mode Measuring conditions HIGH HEAT • Air velocity distribution (ft) Unit: ft/s (m/s) 7 (2) Side view Vertical airflow direction louver: Down 3 (1) Horizontal airflow direction louver: Center 2 (0.5) (ft) • Air temperature distribution (ft) Unit: °F (°C) 86 (30) Side view...
Page 44
¢ Model: ARU18RLF NOTE: This data is measured after installing optional Auto louver grille kit. Fan speed Operation mode Measuring conditions HIGH • Air velocity distribution (ft) Unit: ft/s (m/s) Top view 7 (2) 3 (1) Vertical airflow direction louver: Up 2 (0.5) Horizontal airflow direction louver: Center (ft)
Page 45
Fan speed Operation mode Measuring conditions HIGH HEAT • Air velocity distribution (ft) Unit: ft/s (m/s) 7 (2) Side view Vertical airflow direction louver: Down Horizontal airflow direction louver: Center 3 (1) 2 (0.5) (ft) • Air temperature distribution (ft) Unit: °F (°C) 86 (30) Side view...
5-4. Floor type ¢ Models: AGU9RLF, AGU12RLF, and AGU15RLF Fan speed Operation mode Fan select Measuring conditions HIGH Upper and lower (ft) Unit: ft/s (m/s) 3(1.0) 2(0.5) Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center UPPER LOWER (ft) (ft)
• 3.6 m /h = 1 l/s • 1.699 m /h = 1 CFM 7-1. Compact cassette type Airflow Model Operation mode Fan speed High Cooling Quiet AUU7RLF High Heating Quiet High Cooling Quiet AUU9RLF High Heating Quiet High Cooling...
7-2. Slim duct type Airflow Model Operation mode Fan speed High Cooling Quiet ARU7RLF High Heating Quiet High Cooling Quiet ARU9RLF High Heating Quiet High Cooling Quiet ARU12RLF High Heating Quiet High Cooling Quiet ARU18RLF High Heating Quiet - 55 - 7-2.
7-3. Wall mounted type Airflow Model Operation mode Fan speed High Cooling Quiet ASU7RLF1 High Heating Quiet High Cooling Quiet ASU9RLF1 High Heating Quiet High Cooling Quiet ASU12RLF1 High Heating Quiet High Cooling Quiet ASU15RLF1 High Heating Quiet High Cooling Quiet ASU18RLF High...
7-4. Floor type Airflow Model Operation mode Fan speed High Cooling Quiet AGU9RLF High Heating Quiet High Cooling Quiet AGU12RLF High Heating Quiet High Cooling Quiet AGU15RLF High Heating Quiet - 57 - 7-4. Floor type 7. Airflow...
8-5. Sound level check point ¢ Compact cassette type Microphone Microphone - 67 - 8-5. Sound level check point 8. Noise level curve...
Page 74
¢ Slim duct type 79 in (2 m) 40 in (1 m) Measuring duct Measuring duct Set the static pressure as rating in this area Microphone Microphone Side view Front view ¢ Wall mounted type Microphone Microphone 40 in (1 m) ¢...
11. External input and output External input External output Indoor unit type Operation Fresh air Auxiliary heater Error status Control input status output control output output output Compact ● ● ● ― ― cassette Slim duct ● ● ● ● ―...
Page 78
Circuit diagram example • Contact capacity: DC 24 V or more, 10 mA or more. Indoor unit Connected unit control PCB • *1: PCB of Communication kit is used for wall mounted (ASU7RLF1, ASU9RLF1, and ASU12RLF1) type. Connector Example: Switch •...
Page 79
Optional part Indoor unit type Parts name Model name Compact cassette UTY-XWZX Slim duct UTD-ECS5A ASU7RLF1, ASU9RLF1, ASU12RLF1, External connect kit UTY-XWZXZ5 ASU15RLF1 Wall mounted ASU18RLF UTY-XWZX Floor AGU9RLF, AGU12RLF, AGU15RLF UTY-XWZXZ5 UTY-XWZX UTD-ECS5A UTY-XWZXZ5 Indoor unit type Parts name Model name Compact cassette —...
11-2. External output Use an external output cable with appropriate external dimension, depending on the number of ca- bles to be installed. ¢ Operation status output Indoor unit type Connector Compact cassette CN103 Slim duct CN103 ASU7RLF1, ASU9RLF1, ASU12RLF1, ASU15RLF1 CNB01 Wall mounted ASU18RLF...
Page 81
Optional part Indoor unit type Parts name Model name Compact cassette UTY-XWZX Slim duct UTD-ECS5A ASU7RLF1, ASU9RLF1, ASU12RLF1, External connect kit UTY-XWZXZ5 ASU15RLF1 Wall mounted ASU18RLF UTY-XWZX Floor AGU9RLF, AGU12RLF, AGU15RLF UTY-XWZXZ5 Indoor unit type Parts name Model name Compact cassette —...
Page 82
¢ Fresh air control output Indoor unit type Connector Compact cassette Slim duct Wall mounted — Floor — Signal linked to air conditioner indoor fan on can be output. * However, signal becomes off during cold air prevention control operation. •...
Page 83
¢ Auxiliary heater output Indoor unit type Connector Compact cassette — Slim duct CN10 Wall mounted — Floor Signal is output from connector when indoor fan and compressor turn on under heating operation. *Signal output performance specifications are as shown as follows: Example: When Set Temperature (Ts) is 72 °F(22 °C) •...
Page 84
• Circuit diagram example Indoor unit Connected unit control PCB Example: Example: Heater 12 V Connector Relay unit Relay power On/Off supply 33 ft (10 m)* Signal Locally purchased – Relay spec.: Rated DC 12 V, 50 mA to less. –...
Page 85
¢ Error status output Indoor unit type Connector Compact cassette — Slim duct — ASU7RLF1, ASU9RLF1, ASU12RLF1, ASU15RLF1 CNB02 Wall mounted ASU18RLF — Floor AGU9RLF, AGU12RLF, AGU15RLF CN21 An air conditioner error status signal can be output. Circuit diagram example Indoor unit Connected unit control PCB *1...
Page 86
Optional part Indoor unit type Parts name Model name Compact cassette — — Slim duct — — ASU7RLF1, ASU9RLF1, ASU12RLF1, External connect kit UTY-XWZXZ5 ASU15RLF1 Wall mounted ASU18RLF — — Floor AGU9RLF, AGU12RLF, AGU15RLF External connect kit UTY-XWZXZ5 Indoor unit type Parts name Model name Compact cassette...
12. Group connection Wiring regulation on the remote controllers in the multi split models are reviewed and allowed for group connection. Example of group connection Indoor unit Indoor unit Outdoor unit *Exterior of each device shown above might be different from the actual one. NOTES: •...
12-1. Precautions on creating a group connection Take precautions on items described in this section when creating a group connection in the multi split models. CAUTION Group connection to other refrigerant system between the multi systems with same communication system as shown below is strictly prohibited. Indoor unit Indoor unit Indoor unit...
Page 89
• Maximum wiring length of the remote controller cable: 984 ft (300 m) Even if the maximum wiring length of the product itself is specified as longer than 984 ft (300 m), the maximum length of the remote controller cable will be 984 ft (300 m) if the system is group- connected.
12-2. Remote controller address setting procedure for wireless remote controllers Enter the function setting mode of the wireless remote controller. For details, refer to "Function settings" on page 93. Select the function number “00” (Remote controller address setting), and then select any of the number (Setting value) from 00 to 15.
13. Remote controller 13-1. Wireless remote controller (UTY-LNHUM) ¢ Overview UTY-LNHUM a FAN button Selects the fan speed (AUTO, HIGH, MED, LOW, and QUIET). b START/STOP button Starts and stops operation. c SET button (vertical) Adjusts the vertical airflow direction. d SET button (horizontal) Adjusts the horizontal airflow direction.
Page 92
¢ Specifications Controller Unit: in (mm) Top view 3/4 (19) 2-3/16 (56) Front view Side view Rear view Size (H × W × D) in (mm) 6-11/16 × 2-3/16 × 3/4 (170 × 56 × 19) Weight oz (g) 3 (85) (without batteries) NOTE: Actual number of buttons might be different from the figure above.
13-3. Wired remote controller (UTY-RNNUM) ¢ Overview a START/STOP button Starts and stops operation. b SET TEMP. button Selects the setting temperature. c MODE button Selects the operating mode (AUTO , HEAT ,FAN COOL , and DRY d FAN button Selects the fan speed AUTO ,QUIET , LOW...
Page 96
¢ Specifications Dimensions and other specifications on the wired remote controller are as follows. Unit: in (mm) 4-3/4 (120) 11/16 (18) Front view Side view Size (H × W × D) in (mm) 4-3/4 × 4-3/4 × 11/16 (120 × 120 × 18) Weight oz (g) 5.6 (160)
Page 97
¢ Installation Connection pattern NOTE: Connection pattern is different according to type of Indoor unit. Indoor unit types Connection pattern Compact cassette type Pattern A Slim duct type ASU7RLF1, ASU9RLF1, ASU12RLF1, and Pattern B Wall mounted type ASU15RLF1 ASU18RLF Pattern C Floor type ...
Page 98
2. Connect the remote controller cable. • Connect the cable made in step 1. to the terminal (*1) of optional communication kit. • Connect the cable from the terminal (*2) of communication kit to the indoor unit PCB. CNC01 (for ASU7/9/12/15RLF1: UTY-XCBXZ2) CND01 (for ASU7/9/12/15RLF1: UTY-XCBXZ2) Terminal (*2)
14. Function settings To adjust the functions of this product according to the installation environment, various types of function settings are available. NOTE: Incorrect settings can cause a product malfunction. 14-1. Indoor unit (setting by jumper wire) NOTE: This setting is necessary only for slim duct type. ¢...
14-2. Indoor unit (setting by wireless remote controller) • The function settings of the control of the indoor unit can be changed by this procedure according to the installation conditions. Incorrect settings can cause the indoor unit malfunction. • After the power is turned on, perform the “Function setting” according to the installation conditions using the remote controller.
Page 101
¢ AR-RAH2E/AR-RAH1E Button name and function During address setting mode, indoor unit reject the any operation command from remote con- troller. Function number Refer to Function details. MODE button Setting number - Starts the function setting mode Refer to Function details. - Changes the display digits FAN button START/STOP button...
Page 102
For confirming the custom code, press the TIMER MODE button to send the code to the indoor unit. 2 short beeps Press the MODE button to enter the function setting mode. Select the function number by pressing the or the button.
Page 103
Send the function mode information by pressing the TIMER MODE button once. 2 short beeps Send the function setting information by pressing the START/STOP button once. 2 short beeps will be emitted from the indoor unit when the signal is received correctly. If wrong code is set, no beep sound will be emitted.
Page 104
Resetting the power after setting up all indoor units NOTES: • If the reset is not performed, function cannot be read correctly. • After all the functions have been set, the circuit breaker needs to be switched off for at least 2 minutes.
Page 105
Remote controller custom code setting Custom code setting of wireless remote controller needs to be same as the setting of the indoor unit. When you change the custom code setting of the wireless remote controller, do as follows: Press the START/STOP button until only the clock is displayed on the remote controller dis- play.
Page 106
Press the MODE button again to return to the clock display. The custom code will be changed. • If no buttons are pressed within 30 seconds after the custom code is displayed, the system returns to the original clock display. In this case, start again from step 1. •...
Page 107
¢ AR-REG1U Button name and function During address setting mode, indoor unit reject the any operation command from remote con- troller. Function number Refer to Function details Setting number Refer to Function details MIN HEAT button POWERFUL button Changes the display digits Switches between the setting number (bottom line) and function number (top line)
Page 108
Select the function number by pressing the or the buttons. Each time the MIN. HEAT button is pressed, it switches between the right digit and the left digit. Change digit Change digit Proceed to the setting number by pressing the POWERFUL button. (To return to the function number selection, press the POWERFUL button again.) Select the function number by pressing the or the...
Page 109
Press the button once to transmit the function setting information. 2 short beeps will be emitted from the indoor unit when the signal is received correctly. If wrong code is set, no beep sound will be emitted. 2 short beeps NOTE: Press button within 30 seconds after pressing MODE button.
Page 110
Resetting the power after setting up all indoor units NOTES: • If the reset is not performed, function cannot be read correctly. • After all the functions have been set, the circuit breaker needs to be switched off for at least 2 minutes.
Page 111
Remote controller custom code setting Custom code setting of wireless remote controller needs to be same as the setting of the indoor unit. When you change the custom code setting of the wireless remote controller, do as follows: Press the START/STOP button until only the clock is displayed on the display. Press the MODE button for at least 5 seconds to display the current custom code (initially set to Press the SET TEMP.
Page 112
Remote controller temperature unit To change the displayed temperature unit, press the "°C/°F" switching button to select the preferred temperature unit. (Factory setting is set to “°F”.): - 106 - 14-2. Indoor unit (setting by wireless remote controller) 14. Function settings...
14-3. Indoor unit (setting by wired remote controller) • The function settings of the control of the indoor unit can be changed by this procedure according to the installation conditions. Incorrect settings can cause the indoor unit malfunction. • After the power is turned on, perform the “Function setting” according to the installation conditions using the remote controller.
Page 114
¢ UTY-RNNUM Button name and function During address setting mode, indoor unit reject the any operation command from remote controller. Function number Refer to Function details Remote controller address Setting number Refer to Function details SET TEMP. “V” and “ Λ...
Page 115
Confirm the setting by pressing the TIMER SET button. The data will be transferred to the indoor unit. Not good Good ● Data is not set up on the indoor unit Data is correctly set up on the indoor unit correctly (-- is displayed.) (Flashing display changes to illuminated display.) ●...
14-4. Indoor unit (setting by simple remote controller) • The function settings of the control of the indoor unit can be changed by this procedure according to the installation conditions. Incorrect settings can cause the indoor unit malfunction. • After the power is turned on, perform the “Function setting” according to the installation conditions using the remote controller.
Page 117
¢ UTY-RSNUM Button name and function During address setting mode, indoor unit reject the any operation command from remote controller. Function number Setting number Refer to Function details Refer to Function details Remote controller address START/STOP button Transmits function setting FAN button SET TEMP.
Page 118
Select the setting number by pressing the SET TEMP. or SET TEMP. button. The setting number indicator flashes during setting number selection. Setting number Example) Function number : 30, Setting number : 01 Confirm the setting by pressing the TIMER SET button. The data will be transferred to the indoor unit.
Page 119
Resetting the power after setting up function of all indoor units NOTES: • If the reset is not performed, function cannot be read correctly. • After all the functions have been set, the circuit breaker needs to be switched off for at least 2 minutes.
14-5. Function details ¢ Contents of function setting Each function setting listed in this section is adjustable in accordance with the installation environ- ment. NOTE: Setting will not be changed if invalid numbers or setting values are selected. Function setting list Compact Wall Functions...
Page 121
2) Ceiling height Select the appropriate ceiling height according to the place of installation. Function number Setting value Setting description Factory setting Standard ♦ High ceiling For the specific height for each setting value, refer to “Installation space” in Chapter 3. "Dimensions"...
Page 122
6) Room temperature control for indoor unit sensor NOTE: Before performing this setting, refer to Function 95. Depending on the installed environment, correction of the room temperature sensor may be re- quired. Select the appropriate control setting according to the installed environment. The temperature correction values show the difference from the Standard setting "00"...
Page 123
9) Remote controller custom code (Only for wireless remote controller) The indoor unit custom code can be changed. Select the appropriate custom code. Function number Setting value Setting description Factory setting ♦ 10) External input control "Operation/Stop" mode or "Forced stop" mode can be selected. Function number Setting value Setting description...
Page 124
13) Room temperature control for wired remote controller sensor NOTE: Before performing this setting, refer to Function 95. Depending on the installed environment, correction of the room temperature sensor may be re- quired. Select the appropriate control setting according to the installed environment. To change this setting, set Function 42 to "Both"...
14-6. Wired remote controller Prohibited Dual remote controller setting Prohibited DIP switch 1 °F/°C switch Prohibited Memory backup setting * Do not use DIP switch 2. ¢ Switch location Front case (back side) DIP switch 2 DIP switch 1 ¢ DIP switch 1 setting ...
Page 126
SW6: Memory backup setting Set to “ON” to use batteries for the memory backup. When batteries are not used, all of settings stored in memory will be deleted if there is a power failure. Memory backup Factory setting Disable ♦...
14-7. Simple remote controller Prohibited Dual remote controller setting °F/°C switch DIP switch Prohibited Prohibited Prohibited ¢ Switch location DIP Switch ¢ DIP switch setting SW2: Dual remote controller setting Set the remote controller SW2 according to the following table. Primary unit Secondary unit Number of remote controller...
15-2. Slim duct type ¢ Models: ARU7RLF, ARU9RLF, ARU12RLF, and ARU18RLF Part name Exterior Q’ty Part name Exterior Q’ty Operating manual Cable tie (large) Installation manual Cable tie (small) Installation template Drain hose Washer Hose band Coupler heat insulation Drain hose insulation B (large) Coupler heat insulation Remote controller...
15-3. Wall mounted type ¢ Models: ASU7RLF1, ASU9RLF1, ASU12RLF1, and ASU15RLF1 Part name Exterior Q’ty Part name Exterior Q’ty Operating manual Cloth tape Installation manual Tapping screw (large) Wall hook bracket Tapping screw (small) Remote controller Air cleaning filter Battery Filter holder Seal A •...
Page 131
¢ Model: ASU18RLF Part name Exterior Q’ty Part name Exterior Q’ty Operating manual Drain hose insulation Installation manual Cloth tape Wall hook bracket Tapping screw (large) Remote controller Tapping screw (small) Battery Air cleaning filter Remote controller Air cleaning filter frame holder - 125 - 15-3.
16-3. Others ¢ Lineup Type Air outlet Insulation Fresh air External shutter kit for high External connect kit Indoor unit type intake kit control set plate humidity UTD- UTY- UTR-YDZB UTZ-KXGC UTZ-VXAA UTY-XWZX ECS5A XWZXZ5 Compact cassette ◌ ◌ ◌ —...
Page 136
¢ Parts Air outlet shutter plate Insulation kit for high humidity Model: UTR-YDZB Model: UTZ-KXGC Insulation For compact cassette type For compact cassette type Fresh air intake kit External control set Model: UTZ-VXAA Model: UTD-ECS5A (×1) (×2) (×1) (×2) For compact cassette type For slim duct type External connect kit External connect kit...
17. Indoor unit installation precautions NOTE: The information listed below are general precautions. Some models also include items that do not apply. 17-1. Places where prohibited for use • Places where there is a danger of combustible gas leakage. • Places where sulfur gas, chlorine gas, acid, alkali, or other matter which effects equipment is gen- erated.
17-2. Points to remember when installing • The product shall be installed at a place which can withstand the weight and vibration of the in- door. • To allow maintenance after refrigerant piping, drain piping, and electric wiring connection and in- stallation, provide an installation service space and an inspection port, as required.
Page 139
Work method when reinforcing the heat insulation of on-site piping Slit of heat insulating material Heat insulation reinforcement material Flare connection facing upward (locally purchased) To indoor unit Covered gas pipe (heat insulation strengthened) Fit tightly Heat insulating material Small exposed part Binding material (purpose is to cover the sealant) (locally purchased)
Page 140
- 134 - 17-2. Points to remember when installing 17. Indoor unit installation precautions...
1. Specifications Type Inverter heat pump Model name AOU18RLXFZH Power source 1Ø 208/230 V 60 Hz Available voltage range 187—264V Number Connectable indoor unit Total capacity range 14,000 to 21,000 Btu/h Non-duct Duct Combination of indoor unit ASU9RLF1 × 2 ARU9RLF ×...
3. Installation space 3-1. Model: AOU18RLXFZH ¢ Space requirement Provide sufficient installation space for product safety. Single outdoor unit installation • When the upper space is open: Unit: in (mm) When there are obstacles at the rear only. When there are obstacles at the rear and sides.
Page 145
Multiple outdoor unit installation • When the upper space is open: Unit: in (mm) When there are obstacles at the rear only. When there are obstacles at the front only. 60 (1,500) or more 10 (250) 12 (300) or more or more When there are obstacles at the front and rear.
Page 146
Outdoor unit installation in multi-row Unit: in (mm) Single parallel unit arrangement Multiple parallel unit arrangement 6 (150) or more 20 (500) or more 79 (2,000) or more 119 (3,000) or more 24 (600) or more 24 (600) or more 60 (1,500) or more 40 (1,000) or more 10 (250) or more...
6. Capacity table 6-1. Combinations ¢ Model: AOU18RLXFZH Cooling 1) Non-ducted Rated capacity for each in- Maximum capacity for each Total capacity Combination of indoor unit Input power (kW) door unit (kBtu/h) indoor unit (kBtu/h) (kBtu/h) Room 1 Room 2 Total Room 1 Room 2...
Page 150
Heating 1) Non-ducted Rated capacity for each in- Maximum capacity for each in- Total capacity Combination of indoor unit Input power (kW) door unit (kBtu/h) door unit (kBtu/h) (kBtu/h) Room 1 Room 2 Total Room 1 Room 2 Room 1 Room 2 Min.
6-2. Cooling capacity NOTE: Values mentioned in the table are calculated based on the maximum capacity. ¢ Model: AOU18RLXFZH • TC: Total Capacity, SHC: Sensible Heat Capacity, IP: Input Power • The data is based on the following conditions: Pipe length: 24.6 ft (7.5 m), Height difference: 0 ft (0 m) [Outdoor unit—Indoor unit] ...
6-3. Heating capacity NOTE: Values mentioned in the table are calculated based on the maximum capacity. ¢ Model: AOU18RLXFZH • TC: Total Capacity, IP: Input Power • The data is based on the following conditions: Pipe length: 24.6 ft (7.5 m), Height difference: 0 ft (0 m) [Outdoor unit—Indoor unit] ...
7. Capacity compensation rate for pipe length and height difference Height difference H Indoor unit is higher than outdoor unit Indoor unit is lower than outdoor unit Outdoor unit Indoor unit Outdoor unit Indoor unit Connection pipe Connection pipe 7-1. Model: AOU18RLXFZH NOTE: Values mentioned in the table are calculated based on the maximum capacity.
8. Additional charge calculation 8-1. Model: AOU18RLXFZH Refrigerant type R410A lb oz 4 lb 3 oz Refrigerant amount 1,900 ¢ Refrigerant charge 98 or less 164 (Max.) Total pipe length 0.21 oz/ft 30 or less 50 (Max.) lb oz 7.1 oz 14.1 oz (20 g/m) Additional charge...
11. Electrical characteristics Model name Item Unit AOU18RLXFZH Voltage 208/230 ~ Power supply Frequency MCA *1 19.7 Starting current MAX. CKT. BKR *3 Wiring spec. *2 Power cable *1: Minimum Circuit Ampacity (Calculation based on UL1995) *2: Selected sample based on Japan Electrotechnical Standards and Codes Committee E0005. As the regulations of wire size and circuit breaker differ in each country or region, select appropriate de- vices complied to the regional standard.
12. Safety devices Model Type of protection Protection form AOU18RLXFZH 250 V, 5 A Current fuse (Main PCB) 250 V, 3.15 A Circuit protection Current fuse 250 V, 10 A (Near the terminal) 251 ±16 °F Activate (122 ±9 °C) Fan motor stop Fan motor protection Temperature thermistor...
14. Outdoor unit installation precautions NOTE: The information listed below are general precautions. Some models also include items that do not apply. 14-1. Points to remember when installing • The product shall be installed at a place which can withstand the weight and vibration of the out- door unit.
Page 170
- 164 - 14-1. Points to remember when installing 14. Outdoor unit installation precautions...
1. Specifications Type Inverter heat pump Model name AOU24RLXFZH Power source 1Ø 208/230 V 60 Hz Available voltage range 187—264V Number 2 to 3 Connectable indoor unit Total capacity range 14,000 to 21,000 Btu/h Non-duct Duct Combination of indoor unit ASU9RLF1 + ASU7RLF1 ×...
3. Installation space 3-1. Model: AOU24RLXFZH ¢ Space requirement Provide sufficient installation space for product safety. Single outdoor unit installation • When the upper space is open: Unit: in (mm) When there are obstacles at the rear only. When there are obstacles at the rear and sides.
Page 175
Multiple outdoor unit installation • When the upper space is open: Unit: in (mm) When there are obstacles at the rear only. When there are obstacles at the front only. 60 (1,500) or more 10 (250) 12 (300) or more or more When there are obstacles at the front and rear.
Page 176
Outdoor unit installation in multi-row Unit: in (mm) Single parallel unit arrangement Multiple parallel unit arrangement 6 (150) or more 20 (500) or more 79 (2,000) or more 119 (3,000) or more 24 (600) or more 24 (600) or more 60 (1,500) or more 40 (1,000) or more 10 (250) or more...
6. Capacity table 6-1. Combinations ¢ Model: AOU24RLXFZH Cooling 1) Non-ducted Rated capacity for each indoor Maximum capacity for each in- Total capacity Combination of indoor unit Input power (kW) unit (kBtu/h) door unit (kBtu/h) (kBtu/h) Room 1 Room 2 Room 3 Total Room 1...
Page 180
Heating 1) Non-ducted Rated capacity for each indoor Maximum capacity for each in- Total capacity Combination of indoor unit Input power (kW) unit (kBtu/h) door unit (kBtu/h) (kBtu/h) Room 1 Room 2 Room 3 Total Room 1 Room 2 Room 3 Room 1 Room 2...
6-2. Cooling capacity NOTE: Values mentioned in the table are calculated based on the maximum capacity. ¢ Model: AOU24RLXFZH • TC: Total Capacity, SHC: Sensible Heat Capacity, IP: Input Power • The data is based on the following conditions: Pipe length: 7.5 m, Height difference: 0 m [Outdoor unit—Indoor unit] ...
6-3. Heating capacity NOTE: Values mentioned in the table are calculated based on the maximum capacity. ¢ Model: AOU24RLXFZH • TC: Total Capacity, IP: Input Power • The data is based on the following conditions: Pipe length: 24.6 ft (7.5 m), Height difference: 0 ft (0 m) [Outdoor unit—Indoor unit] ...
7. Capacity compensation rate for pipe length and height difference Height difference H Indoor unit is higher than outdoor unit Indoor unit is lower than outdoor unit Outdoor unit Indoor unit Outdoor unit Indoor unit Connection pipe Connection pipe 7-1. Model: AOU24RLXFZH NOTE: Values mentioned in the table are calculated based on the maximum capacity.
8. Additional charge calculation 8-1. Model: AOU24RLXFZH Refrigerant type R410A lb oz 4 lb 14 oz Refrigerant amount 2,200 ¢ Refrigerant charge 98 or less 229 (Max.) Total pipe length 0.21 oz/ft 30 or less 70 (Max.) lb oz 7.1 oz 14.1 oz 21.2 oz 28.2 oz...
11. Electrical characteristics Model name Item Unit AOU24RLXFZH Voltage 208/230 ~ Power supply Frequency MCA *1 25.1 Starting current MAX. CKT. BKR *3 Wiring spec. *2 Power cable *1: Minimum Circuit Ampacity (Calculation based on UL1995) *2: Selected sample based on Japan Electrotechnical Standards and Codes Committee E0005. As the regulations of wire size and circuit breaker differ in each country or region, select appropriate de- vices complied to the regional standard.
12. Safety devices Model Type of protection Protection form AOU24RLXFZH 250 V, 5 A Current fuse (Main PCB) 250 V, 3.15 A Circuit protection Current fuse 250 V, 10 A (Near the terminal) 251 ±16 °F Activate (122 ±9 °C) Fan motor stop Fan motor protection Temperature thermistor...
13. Accessories Part name Exterior Q’ty Part name Exterior Q’ty Adapter assy Installation manual 1/2 in → 3/8 in (12.70 mm) → (9.52 mm) - 205 - 13. Accessories...
14. Outdoor unit installation precautions NOTE: The information listed below are general precautions. Some models also include items that do not apply. 14-1. Points to remember when installing • The product shall be installed at a place which can withstand the weight and vibration of the out- door unit.