Fronius Selectiva 2100 Service Manual page 96

Table of Contents

Advertisement

Available languages

Available languages

24
25
26
Status codes in the event of a charging error:
31
32
34
35
36
37
38
Status codes in the event of a device fault / primary circuit:
500
501
502
96
Cause: Battery too hot (external temperature sensor only)
Remedy:
-
Check battery and if necessary, place in a suitable environment
-
Check device settings
Cause: Battery too cold (external temperature sensor only)
Remedy:
-
Check battery and if necessary, place in a suitable environment
-
Check device settings
Cause: Cell fault detected
Remedy:
-
Check battery
Cause: Time exceeded in I1 phase
Remedy:
-
Check device setting for battery capacity (Ah)
-
Check battery voltage, water level, etc.
Cause: Time exceeded in U1 phase
Remedy:
-
Check device setting for battery capacity (Ah)
-
Check battery voltage, water level, etc.
Cause: Ah exceeded
Remedy:
-
Check device setting for battery capacity (Ah)
-
Check battery voltage, water level, etc.
Cause: Time exceeded in I2 phase
Remedy:
-
Check device setting for battery capacity (Ah)
-
Check battery voltage, water level, etc.
Cause: Target voltage not reached in I2 phase (format characteristic only)
Remedy:
-
Check battery voltage, water level, etc.
Cause: Time exceeded during Ri charging, power derating of device
Remedy:
-
Check device setting for battery capacity (Ah)
-
Check battery voltage, water level, etc.
Cause: The time in which the battery has to be completely charged is too short
Remedy:
-
Check set time
Cause: Module 1 (top) temperature sensor faulty
Remedy:
-
Replace primary power module
Cause: Module 2 (bottom) temperature sensor faulty
Remedy:
-
Replace primary power module
Cause: PCB temperature sensor faulty
Remedy:
-
Replace primary power module