Mitsubishi L02CPU User Manual page 137

Melsec-l series
Hide thumbs Also See for L02CPU:
Table of Contents

Advertisement

Function
Specification
format
password-lock
Example
*2
Use this command only when the FTP communication port is specified as a remote password check target.
Function
Specification
format
Example 1
run
Example 2
Example 3
Note
Function
Specification
status
format
Function
Specification
format
stop
Note
Locks the remote password set in the CPU module.
quote password-lock
The following is displayed as the execution result when the processing completes
successfully.
200 Command 0key
When locking the remote password:
quote password-lock
Sets the CPU module to the RUN state (remote RUN).
At this time, device memory clear can be specified.
quote run [mode [clear mode]]
• Mode: Specify whether to forcibly execute remote RUN or not.
0: Normal RUN (default)
1: Forced RUN
• Specify the CPU module device memory clear (initialization) processing performed when
the operation starts by executing remote RUN.
0: Do not clear device. (default)
1: Clear other than the latch range.
2: Clear all including the latch range.
The following message is displayed as the execution result when the processing completes
successfully.
200 Command successful
When executing remote RUN, with "Normal RUN" and "Do not clear device." specified:
quote run
When executing remote RUN, with "Forced RUN" and "Do not clear device." specified:
quote run 1
When executing remote RUN, with "Forced RUN" and "Clear other than the latch range."
specified:
quote run 1 1
• Forced RUN should be used only to force remote RUN to the CPU module from another
device when a device that executed remote STOP to the CPU module have a problem
and cannot perform remote RUN. With Normal RUN, the operating status of the CPU
module cannot be changed from STOP/PAUSE to RUN if the status has been set by a
different device.
• Specify the clear mode at the start of an operation, according to the system arrangement.
After completing the specified clear processing, the CPU module runs in accordance with
the PLC parameter setting ("Initial Device value" setting on the "PLC File" tab).
Displays the operating status of the CPU module.
This command is used to check the operating status of the CPU module when transferring
files to the CPU module.
quote status
One of the following is displayed as the execution result when the processing completes
successfully.
• When the CPU module is in RUN state: "RUN"
• When the CPU module is in STOP state: "STOP"
• When the CPU module is in PAUSE state: "PAUSE"
Sets the CPU module to the STOP state (remote STOP).
quote stop
The following message is displayed as the execution result when the processing completes
successfully.
200 Command successful
Before writing data to the program memory, set the CPU module to the STOP state using
this command.
CHAPTER 9 FILE TRANSFER FUNCTION (FTP SERVER)
*2
9