Siemens SENTRON PAC3100 Manual page 106

Power monitoring device
Hide thumbs Also See for SENTRON PAC3100:
Table of Contents

Advertisement

Technical data
11.1 Technical data
Measuring inputs for current
Only for connection to AC power systems via external current transformers
Input current I
Max. permissible continuous current
Current impulse overload capability
Zero point suppression level
Max. power consumption per phase
Measuring accuracy
Measured variable
Voltage
Current
Apparent power
Active power
Reactive power
Total apparent power over all phases
Total active power over all phases
Total reactive power VAR1 over all phases
Cumulated active power
Cumulated reactive power
Total power factor
Line frequency
Active energy
Reactive energy
When measuring on external current transformers or voltage transformers, the accuracy of
the measurement depends on the quality of the transformer.
Power supply
Design of the power supply
Rated range
Work area
Power consumption
Overvoltage category
106
I
throughout phases
in the neutral conductor
x / 5 A 3 AC (+ 20%)
10 A
100 A for 1 s
10 mA
45 mA
500 mVA at 6 A
Accuracy class in accordance with
IEC 61557-12:2007-08 (K55)
1
1
1
1
3
1
1
3
1
3
2
0,1
1
3
Wide-range power supply AC / DC
100 ... 240 V AC (45 ... 65 Hz) or
110 ... 250 V DC
± 10% of AC/DC rated range
5 W DC / 10 VA AC
CAT III
Manual, 07/2009, A5E02385159B-01
SENTRON PAC3100