Setting The Conversion Ratio Of The Voltage Transformer; Figure 7-6 "Use Pts?" Device Setting Switched On - Siemens SENTRON PAC3100 Manual

Power monitoring device
Hide thumbs Also See for SENTRON PAC3100:
Table of Contents

Advertisement

7.3.2.3

Setting the conversion ratio of the voltage transformer

The factory setting is measurement direct on the system. At initial startup, the following steps
must be carried out if you want to measure using voltage transformers.
The conversion ratio can only be set if measurement using voltage transformers is set in the
device settings. Only then are the fields for primary and secondary voltage visible on the
display.
Figure 7-6
Procedure
1. In the "SETTINGS" menu, call the "BASIC PARAMETERS" entry.
2. In the "BASIC PARAMETERS" menu, open the "VOLTAGE INPUTS" entry:
<F4>
The display shows the current settings.
If the "PT PRIMARY" and "PT SECONDARY" fields are not visible, direct measurement
on the system is set. Switch from direct measurement to measurement using voltage
transformers. You can find the instructions for this in the "Measurement using voltage
transformers" chapter.
3. Go to the "PT PRIMARY" device setting:
<F2>
4. Open edit mode of the "PT PRIMARY" device setting:
<F4>
5. Set the desired value:
<F2>
6. Accept the value:
<F4>
The value of the primary voltage is permanently saved and becomes effective
immediately.
The display returns to display mode.
7. Go to the "PT SECONDARY" device setting:
<F2>
Proceed in exactly the same way as when entering the primary voltage.
The value of the secondary voltage is permanently saved and becomes effective
immediately.
The display returns to display mode.
8. Return to one of the selection menus or to the measured values display:
<F1>
SENTRON PAC3100
Manual, 07/2009, A5E02385159B-01
"USE PTs?" device setting switched on
or <F3>
or <F3>
or <F3>
Commissioning
7.3 Parameterizing the device
57