Deinstallation steps
1. Discharge any static from your body in accordance with the ESD guidelines.
2. Start deinstallation on the inside of the switching panel.
3. Release the clamping arrangement on the switching panel. To do so, unscrew the four
screws on the two brackets. Leave the screws in the brackets.
4. Carefully lever the locking hooks open with the slotted screwdriver or another suitable
tool. The bracket releases immediately.
5. Go to the outside of the switching panel and remove the device from the cutout.
6. Pack the device into the original box together with the operating instructions and the
delivered components listed in the operating instructions.
Deinstallation is complete.
Figure 5-1
Deinstallation, releasing the locking hooks
See also
ESD guidelines (Page 143)
SENTRON PAC3100
Manual, 07/2009, A5E02385159B-01
CAUTION
Electrostatic sensitive devices
Discharge your body of any static electricity. Touch the grounded control cabinet, for
example, or a metal part that is connected to the building ground (heater, steel support).