7.3.2
Voltage input
7.3.2.1
Setting the connection type
Inform the device of the connection type executed. To do so, enter the short code for the
connection type in the device settings.
Note
Connection type
The connection type executed must agree with the connection type entered in the device.
Table 7- 2
Short code
3P4W
3P3W
You can find further information on the possible connection types, and on how the measured
value representation depends on the connection type, in the "Description" chapter.
Procedure
1. Exit the measured value display and call the "MAIN MENU":
<F4>
2. In the main menu, go to the "SETTINGS" entry:
<F2>
3. Call the "SETTINGS" entry:
<F4>
4. In the "SETTINGS" menu, go to the "BASIC PARAMETERS" entry:
<F2>
5. Call the "BASIC PARAMETERS" entry:
<F4>
6. In the "BASIC PARAMETERS" menu, call the "VOLTAGE INPUTS" entry:
<F4>
The display shows the currently valid settings.
Figure 7-4
SENTRON PAC3100
Manual, 07/2009, A5E02385159B-01
Available connection types
or <F3>
or <F3>
"CONNECTION TYPE" device setting
7.3 Parameterizing the device
Connection type
3 phases, 4 conductors, unbalanced load
3 phases, 3 conductors, unbalanced load
Commissioning
55