Fail Safe Electric Strike or Electromagnetic Lock 24VDC Wiring

Change Factory Pre-Wiring from Illustration A to Illustration B (more NO to NC)
A)
Fail Safe Electric Strike 24VDC
Wiring
Doors are normally closed and
Ÿ
latched.
Activating switch will unlock
Ÿ
electric strike or mag lock and
door will automatically open. Door
will close after hold open time
delay has expired.
The door will remain unlocked
Ÿ
during power failure.
Current draw at Power Outputs not
Ÿ
to exceed 1.3 amps.

24VDC Electric Exit Device Wiring

Factory Pre-Wiring in Illustration is for this functionality.
24VDC Electric Exit Device
Wiring
Ÿ
Doors are normally closed and
latched.
Activating switch will energize exit
Ÿ
device and door will automatically
open. Exit device will stay
energized based on Latch Rtrct
setting. Door will close after hold
open time delay has expired.
Current draw at Power Outputs not
Ÿ
to exceed 1.3 amps.
Copyright © 2015 Yale Security Inc., an ASSA ABLOY Group company. All rights reserved.
Reproduction in whole or in part without the express written permission of Yale Security Inc. is prohibited.
B)
24VDC
Electric Strike
(Fail Secure)
+
-
+
-
Wall Switch, Card Reader,
Key Switch, etc.
(Normally Open
Momentary dry contacts)
Page 15
ASSA ABLOY
+
-
24VDC
Electromagnetic
Lock (Fail Safe)
Wall Switch, Card
Reader, Key Switch, etc.
(Normally Open
Momentary dry contacts)
24VDC Electric Exit Device