ABB REF 610 Technical Reference Manual page 96

Feeder protection relay
Hide thumbs Also See for REF 610:
Table of Contents

Advertisement

REF 610
96
Feeder Protection Relay
Technical Reference Manual - ANSI Version
Table 4.1.16.4-1 Supported function codes
Code Function
Response Function Codes
0
Confirm
129
Response
130
Unsolicited Message
1)
Counters of REF 610 can not be cleared using the DNP 3.0 protocol.
Table 4.1.16.4-2 Supported objects
OBJECT
Object
Variation
group
1
0
Binary Input, all variations
1
1
Binary Input
1
2
Binary Input with Status
2
0
Binary Input Change, all
variations
2
1
Binary Input Change without
Time
2
2
Binary Input Change with Time
2
3
Binary Input Change with
Relative Time
10
0
Binary Output, all variations
10
1
Binary Output
10
2
Binary Output with Status
12
0
Control Block, all variations
12
1
Control Relay Output Block
12
2
Pattern Control Block
12
3
Pattern Mask
20
0
Binary Counter, all variations
20
1
32-Bit Binary Counter
20
2
16-Bit Binary Counter
20
3
32-Bit Delta Counter
20
4
16-Bit Delta Counter
Description
Message fragment confirmation
Response to request message
Spontaneous message without
request
REQUEST
(slave must parse)
Function
Description
Codes
(dec)
1, 20,
21, 22
1, 20,
21, 22
1, 20,
21, 22
1
1
1
1, 7, 8,
20, 21,
22
1, 7, 8,
20, 21,
22
1, 7, 8,
20, 21,
22
1MRS 755535
Supported
Yes
Yes
Yes
RESPONSE
(master must parse)
Qualifier
Function
Qualifier
Codes
Codes
Codes
(hex)
(dec)
(hex)
00, 01,
129
00, 01,
06, 07,
17, 28
08,
17,28
00, 01,
129
00, 01,
06, 07,
17, 28
08,
17,28
00, 01,
129
00, 01,
06, 07,
17, 28
08,
17,28
06, 07,
08
06, 07,
129,
17, 28
08
130
06, 07,
129,
17, 28
08
130
00, 01,
129
00, 01,
06, 07,
17, 28
08,
17,28
00, 01,
129
00, 01,
06, 07,
17, 28
08,
17,28
00, 01,
129
00, 01,
06, 07,
17, 28
08,
17,28

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents