REF 610
1.
1.1.
1.2.
1.3.
6
Feeder Protection Relay
Technical Reference Manual - ANSI Version

Introduction

About this manual

This manual provides thorough information on the protection relay
and its applications
Revision B
refer to section "Revision history of the REF 610".
Refer to the Operator's Manual for instructions on how to use the
Human-Machine Interface (HMI) of the relay, also known as the Man-Machine
Interface (MMI), and to the Installation Manual for installation of the relay.

The use of the relay

The feeder protection relay REF 610 is a versatile multifunction protection relay
mainly designed to protect incoming and outgoing feeders in a wide range of feeder
applications.
REF 610 is based on a microprocessor environment. A self-supervision system
continuously monitors the operation of the relay.
The HMI includes a Liquid Crystal Display (LCD) which makes the local use of the
relay safe and easy.
Local control of the relay via serial communication can be carried out with a
computer connected to the front communication port. Remote control can be carried
out via the rear connector connected to the control and monitoring system through
the serial communication bus.

Features

• Three-phase non-directional overcurrent protection with definite-time or IDMT
(mode) characteristic, low-set element
• Three-phase non-directional overcurrent protection, high-set element
• Three-phase non-directional overcurrent protection, instantaneous element
• Non-directional ground-fault protection with definite-time or IDMT (mode)
characteristic, low-set element
• Non-directional ground-fault protection, high-set element
• Phase discontinuity protection
• Three-phase thermal overload protection for cables
• Arc protection
• two lens sensors for arc detection (optional)
• automatic reference level adjustment based on backlight intensity
• arc detection via a remote light signal
• Automatic reclosing 1...3 shots
• Circuit-breaker failure protection
• Trip counters for circuit-breaker condition monitoring
• Trip-circuit supervision with possibility to route the warning signal to a non-trip
output
. For more information about the earlier revisions,
1MRS 755535
REF 610