ABB REF 610 Technical Reference Manual page 88

Feeder protection relay
Hide thumbs Also See for REF 610:
Table of Contents

Advertisement

REF 610
88
Feeder Protection Relay
Technical Reference Manual - ANSI Version
Table 4.1.15.2-6 Fault record
Address Signal name
623
Pickup duration of element 50N
624
Pickup duration of element 46
625
Pickup duration of external trip
626
Trip number of AR sequence
627
Pickup duration of element ARC (local)
628
Pickup duration of element ARC (remote) 0/100
1)
Readable and writeable register.
Structure 3
This structure contains Modbus event records. Refer to section Event records for the
reading method.
Table 4.1.15.2-7 Event record
Address Signal name
671
Latest selection code
672
Sequence number
673
Unread records left
674
Time stamp of the event, date
675
Time stamp of the event, date and
time
676
Time stamp of the event, time
677
Time stamp of the event, time
678
Modbus DI point or informative event
(SPA channel)
• DI event
• Informative event
679
DI value or SPA event code
• DI event
• Informative event
1)
Readable and writeable register.
Range
0...100
0...100
0/100
0...255
0/100
Range
1)
1...3
-1...-99
1...255
0...99
0...999
0/1
0
1
0/1
0...63
1MRS 755535
Comment
0...100%
0...100%
0/100%
0/100%
0/100%
Comment
1 = read oldest
unread record
2 = read oldest
stored record
3 = clear Modbus
event buffer
-1...-99 = move to
the nth newest
record
2 bytes: YY.MM
2 bytes: DD.HH
2 bytes: MM.SS
0...999 ms
When MSB = 0, bits
14...0 indicate the DI
point.
When MSB = 1, bits
14...0 indicate the
SPA channel.
In case of a DI
event, the register
will contain the DI
value.
In case of an
informative event,
the register will
contain the SPA
event code.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents