ABB REF 610 Technical Reference Manual page 154

Feeder protection relay
Hide thumbs Also See for REF 610:
Table of Contents

Advertisement

REF 610
154
Feeder Protection Relay
Technical Reference Manual - ANSI Version
Table 10.-2Setting group 2
Variable
Time multiplier 51P TD
ANSI
Resetting time of element
51P (51P RSET)
Pickup value of element
50P-1
Operate time of element
50P-1 (50P-1 TDLY)
Pickup value of element
50P-2
Operate time of element
50P-2 (50P-2 TDLY)
Pickup value of element
51N
Operate time of element
51N (51N TDLY)
Time/current characteristic
for element 51N
Time multiplier 51N TD IEC
Time multiplier 51N TD
ANSI
Resetting time of element
51N (51N RSET)
Pickup value of element
50N
Operate time of element
50N (50N TDLY)
Pickup value of element 46
Operate time of element 46
Full load current
Time constant of element
49
Alarm level of element 49
CBFAIL
Operate time of
(Trip Fail)
Number of AR shots
Arc50P
Current limit
of
element ARC
Current limit Arc51N of
2)
element ARC
Checksum, SGF 1
Checksum, SGF 2
Checksum, SGF 3
Checksum, SGF 4
Checksum, SGF 5
Group/
Channel 2
Setting range
(R, W, P)
2S5
1.0...15.0
2S6
0.05...2.50 s
2S7
0.50...35.0 x
I
n
2S8
0.04...300 s
2S9
0.50...35.0 x
I
n
2S10
0.04...30.0 s
2S11
1.0...100%
I
(CT)
n
2S12
0.05...300 s
2S13
0...8
2S14
0.05...1.00 s
2S15
1.0...15.0
2S16
0.05...2.50
2S17
5.0...400%
I
(CT)
n
2S18
0.05...300 s
2S19
10...100%
2S20
1...300 s
2S21
0.30...1.50 x
I
n
2S22
1...200 min
2S23
50...100% 49 Trip
2S24
0.10...60.0 s
2S25
0 = AR is not in use
1 = shot 1
2 = shot 1 and 2
3 = shot 1, 2 and 3
2S26
0.50...35.0 x
I
n
2S27
5.0...400%
I
(CT)
n
2S61
0...255
2S62
0...127
2S63
0...127
2S64
0...63
2S65
0...255
1MRS 755535
Default
Customer'
setting
s setting
1.0
0.05 s
0.50 x
(CT)
I
(CT)
n
0.04 s
0.50 x
(CT)
I
(CT)
n
0.04 s
1.0%
I
(CT)
n
0.05 s
0
0.05 s
1.0
0.05
5.0%
I
(CT)
n
0.05 s
100%
60 s
0.30 x
(CT)
I
(CT)
n
1 min
95% 49 Trip
0.10 s
0
2.50 x
(CT)
I
(CT)
n
20%
I
(CT)
n
0
0
120
0
0