ABB REF 610 Technical Reference Manual page 87

Feeder protection relay
Hide thumbs Also See for REF 610:
Table of Contents

Advertisement

1MRS 755535
Feeder Protection Relay
Technical Reference Manual - ANSI Version
Structure 1
The status registers contain information on unread fault and event records, and relay
status. The registers are arranged as in the figure below.
15
401
Reserved
402
403
FR ER
Fig. 4.1.15.2.-2 Status registers
When the value of the FR/ER bit is 1, there is one or several unread fault/event
records. If time synchronization is realized via a digital input, either the SP
(second-pulse) or MP (minute-pulse) bit will be activated. Refer to table 4.1.18-1
for IRF codes and table 4.1.18-2 for warning codes.
Structure 2
This structure contains data recorded during a fault sequence. Refer to section Fault
records for the reading method.
Table 4.1.15.2-6 Fault record
Address Signal name
601
Latest selection code
602
Sequence number
603
Unread records left
604
Time stamp of the recorded data, date
605
Time stamp of the recorded data, date and
time
606
Time stamp of the recorded data, time
607
Time stamp of the recorded data, time
608
Phase current l
609
Phase current l
610
Phase current l
611
Ground-fault current
612
Phase discontinuity
613
Thermal level at pickup
614
Thermal level at trip
615
Maximum pick-up phase current l
616
Maximum pick-up phase current l
617
Maximum pick-up phase current l
618
Maximum pick-up ground-fault current
619
Pickup duration of element 51P
620
Pickup duration of element 50P-1
621
Pickup duration of element 50P-2
622
Pickup duration of element 51N
8
7
IRF code
Warning code
Reserved
1)
a
b
c
a
b
c
REF 610
0
SP MP
StatRegREF610_a
Range
Comment
1...2
1 = read oldest
unread record
2 = read oldest
stored record
1...255
0...6
2 bytes: YY.MM
2 bytes: DD.HH
2 bytes: MM.SS
0...999
0...999 ms
0...5000
0...50 x
I
0...5000
0...50 x
I
0...5000
0...50 x
I
0...800
0...800%
0...100
0...100%
0...106
0...106%
0...106
0...106%
0...5000
0...50 x
I
0...5000
0...50 x
I
0...5000
0...50 x
I
0...800
0...800%
0...100
0...100%
0...100
0...100%
0...100
0...100%
0...100
0...100%
(CT)
n
(CT)
n
(CT)
n
I
(CT)
n
I
(CT)
n
(CT)
n
(CT)
n
(CT)
n
I
(CT)
n
87