1MRS 755535
Feeder Protection Relay
Technical Reference Manual - ANSI Version
Fig. 4.2.3.-1
Jumper location on the RS-485 communication module
Table 4.2.3-2
RS-485 rear connector
Terminal
Function
X5.5-6
Data A (+)
X5.5-5
Data B (-)
X5.5-4
Signal GND (for potential balancing)
X5.5-3
-
X5.5-2
Shield GND (via capacitor)
X5.5-1
Shield GND
Combined fibre-optic connection (plastic and glass)
If REF 610 is provided with the optional fibre-optic communication module for
plastic and glass fibre, the plastic fibre-optic cables are connected to terminals
X5.3-RX (Receiver) and X5.3-TX (Transmitter) and the glass fibre-optic cables to
terminals X5.4-RX (Receiver) and X5.4-TX (Transmitter).
The fibre-optic interface is selected with jumpers X6 and X2 located on the PCB of
the communication module (see Fig. 4.2.3.-2).
Table 4.2.3-3
Transmitter selection
Transmitter
Position of jumper X6
Plastic
X5.3-TX
Glass
X5.4-TX
off
X3
on
off
X4
on
off
X5
on
RS_JumpersREF610_a
REF 610