ABB REF 610 Technical Reference Manual page 54

Feeder protection relay
Hide thumbs Also See for REF 610:
Table of Contents

Advertisement

REF 610
54
Feeder Protection Relay
Technical Reference Manual - ANSI Version
Table 4.1.4.10-8 SGR1...SGR3
Switch
Function
SGR1...8/1 Pickup signal from element
51P
SGR1...8/2 Trip signal from element 51P
SGR1...8/3 Pickup signal from element
50P-1
SGR1...8/4 Trip signal from element 50P-1
SGR1...8/5 Pickup signal from element
50P-2
SGR1...8/6 Trip signal from element 50P-2
SGR1...8/7 Pickup signal from element
51N
SGR1...8/8 Trip signal from element 51N
SGR1...8/9 Pickup signal from element
50N
SGR1...8/10 Trip signal from element 50N
SGR1...8/11 Pickup signal from element 46
SGR1...8/12 Trip signal from element 46
SGR1...8/13 Alarm signal from element 49
SGR1...8/14 Trip signal from element 49
SGR1...8/15 External trip signal
SGR1...8/16 Open CB command from AR
SGR1...8/17 Close CB command from AR
SGR1...8/18 Definite trip alarm signal from
AR
SGR1...8/19 CB reclosing failed signal from
AR
SGR1...8/20 Shot due signal from AR
SGR1...8/21 Lockout signal from AR
SGR1...8/22 Trip signal from element ARC
SGR1...8/23 Light signal output
ΣSGR1...8
1)
If the optional I/O module has not been installed, dashes will be shown on the LCD and "9999999"
when the parameter is read via the SPA bus.
SGL1...SGL8
The signals are routed to LED1 with the switches of switchgroup SGL1, to LED2
with those of SGL2, and so forth.
Table 4.1.4.10-9 SGL1...SGL8
Switch
Function
SGL1...8/1
Trip signal from element 51P
SGL1...8/2
Trip signal from element 50P-1
SGL1...8/3
Trip signal from element 50P-2
SGL1...8/4
Trip signal from element 51N
SGL1...8/5
Trip signal from element 50N
Default setting
SGR1...SGR3 SGR4...SGR5 SGR6...SGR8
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
0
0
0
2108074
5461
1MRS 755535
1)
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Default setting