ABB REF 610 Technical Reference Manual page 47

Feeder protection relay
Hide thumbs Also See for REF 610:
Table of Contents

Advertisement

1MRS 755535
Feeder Protection Relay
Technical Reference Manual - ANSI Version
Table 4.1.4.10-1 Setting values
Setting
Description
τ
Time constant of element 49
Alarm level of element 49
49 Alarm
CBFAIL
Operate time of CBFAIL
79
Number of AR shots
Arc50P
Current limit Arc51P of element ARC 0.50...35.0 x
Arc50N
Current limit Arc51N of element ARC 5.0...400%
REF 610
Setting range
Default setting
1...200 min
1 min
50...100% 49 trip
95% 49 trip
0.10...60.0 s
0.10 s
0 = AR is not in use
0
1 = shot 1
2 = shot 1 and 2
3 = shot 1, 2 and 3
2.50 x
I
(CT)
n
20.0%
I
(CT)
n
I
(CT)
n
I
(CT)
n
47