REF 610
106
Feeder Protection Relay
Technical Reference Manual - ANSI Version
Recorded data
Parameter V1 shows the element which has caused the trip, parameter V2 the trip
target code, parameters V3...V8 show the number of pickups of the protection
elements, parameters V9...V12 the number of trips of the protection elements, and
parameters V13...V24 the number of initiated auto-reclose shots.
Table 4.1.17-3 Recorded data: Channel 0
Recorded data
Element/phase which caused the trip
Trip target code
Number of pickups of element 51P
Number of pickups of element 50P-1
Number of pickups of element 50P-2
Number of pickups of element 51N
Number of pickups of element 50N
Number of pickups of element 46
Number of trips of element 50P-1
Number of trips of element 50P-2
Parameter (R) Value
V1
1=Ic(51P)
2=lb(51P)
4=la(51P)
8=51N
16=lc(50P-1)
32=lb(50P-1)
64=la(50P-1)
128=50N
256=lc(50P-2)
512=lb(50P-2)
1024=la(50P-2)
2048=46
4096=49
8192=external trip
16384=AR
32768=trip of element ARC (local)
65536=trip of element ARC
(remote)
V2
0 = ---
1=pickup of element 51P
2=trip of element 51P
3=pickup of element 50P-1
4=trip of element 50P-1
5=pickup of element 50P-2
6=trip of element 50P-2
7=pickup of element 51N
8=trip of element 51N
9=pickup of element 50N
10=trip of element 50N
11=pickup of element 46
12=trip of element 46
13=alarm of element 49
14=trip of element 49
15=external trip
16=definite trip alarm
17=CB reclosing failed
18=AR shot due
19=AR lockout
20=trip of element ARC
21=CBFAIL
V3
0...999
V4
0...999
V5
0...999
V6
0...999
V7
0...999
V8
0...999
V10
0...65535
V11
0...65535