REF 610
52
Feeder Protection Relay
Technical Reference Manual - ANSI Version
Table 4.1.4.10-7 SGB1...SGB5
Switch
Function
SGB1...5/5
Time synchronization by the digital input signal
SGB1...5/6
External tripping by the digital input signal
SGB1...5/7
External triggering of the CBFAIL by the digital input signal
SGB1...5/8
External triggering of the trip lockout by the digital input signal
SGB1...5/9
External arc signalling by the digital input signal
SGB1...5/10
Resetting of the trip lockout by the digital input signal
SGB1...5/11
Blocking of tripping of element 51P by the digital input signal
SGB1...5/12
Blocking of tripping of element 50P-1 by the digital input signal
SGB1...5/13
Blocking of tripping of element 51N by the digital input signal
SGB1...5/14
Blocking of tripping of element 50N by the digital input signal
SGB1...5/15
Blocking of tripping of element 46 by the digital input signal
SGB1...5/16
External AR disable by the digital input signal
SGB1...5/17
External disable of CB reclosing by the digital input signal
SGB1...5/18
CB position open
SGB1...5/19
CB position closed
SGB1...5/20
External AR initiation by the digital input signal
ΣSGB1...5
SGR1...SGR8
The pickup, trip and alarm signals from the protection elements, the signals from the
auto-reclose function, and the external trip signal are routed to the output contacts
with the switches of switchgroups SGR1...SGR8. The signals are routed to
PO1...PO3 with the switches of switchgroup SGR1...SGR3 and to SO1...SO5 with
those of SGR4...SGR8.
The matrix below can be of help when making the desired selections. The pickup,
trip and alarm signals from the protection elements, the signals from the auto-reclose
function and the external trip signal are combined with the output contacts by
encircling the desired intersection point. Each intersection point is marked with a
switch number, and the corresponding weighting factor of the switch is shown to the
right in the matrix. The switchgroup checksum is obtained by vertically adding the
weighting factors of all the selected switches of the switchgroup.
Note!
The trip lockout signal is always routed to PO3.
Note!
The trip signal from CBFAIL is always routed to PO2.
Note!
The external fault warning is always routed to SO2.
1MRS 755535
Default
setting
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0