ABB REF 610 Technical Reference Manual page 125

Feeder protection relay
Hide thumbs Also See for REF 610:
Table of Contents

Advertisement

1MRS 755535
Feeder Protection Relay
Technical Reference Manual - ANSI Version
The IRF contact functions as an output contact for the self-supervision system of the
protection relay (see table 4.2.1-3). Under normal operating conditions the relay is
energized and the contact closed (X4.1/3-5). When a fault is detected by the
self-supervision system or the auxiliary voltage is disconnected, the output contact
will drop off and the contact close (X4.1/3-4).
Fig. 4.2.1.-1...Fig. 4.2.1.-3 present a rear view of REF 610, showing four connecting
sockets: one for measuring transformers, one for the optional I/O module, one for
power supply and one for optional serial communication.