ABB REF 610 Technical Reference Manual page 156

Feeder protection relay
Hide thumbs Also See for REF 610:
Table of Contents

Advertisement

REF 610
156
Feeder Protection Relay
Technical Reference Manual - ANSI Version
Table 10.-3Control parameters
Description
Optional communication
module
Table 10.-4Parameters for the disturbance recorder
Description
Sampling rate
Station identification/unit
number
Name of the feeder
Analogue channel
conversion factor and unit
for l
, l
and l
a
b
c
Analogue channel
conversion factor and unit
for the ground-fault current
Internal trigger signals'
checksum
Internal trigger signal's
edge
Checksum of internal signal
storing mask
Post-triggering recording
length
External trigger signal's
checksum
External trigger signal's
edge
Checksum of external
signal storing mask
Table 10.-5Auto-reclose parameters
Description
CB Closing time
Pickup delay of element
51P
Pickup delay of element
51N
Reclaim time
Cutout time
Dead time of shot 1
Dead time of shot 2
Dead time of shot 3
SG1
SG2
SG3
Parameter
Setting range
(channel 0)
V206
0 = not in use
1 = in use
Parameter
Setting range
(channel 0)
M15
800/960 Hz
400/480 Hz
50/60 Hz
M18
0...9999
M20
Max 16 characters
M80, M81 Factor 0...65535, unit
(A, kA), e.g. 10,kA
M83
Factor 0...65535, unit
(A, kA), e.g. 10,kA
V236
0...16383
V237
0...16383
V238
0...16383
V240
0...100%
V241
0...31
V242
0...31
V243
0...31
Parameter
Value
(channel 0)
V121
0.1...10 s
V122
0...300 s
V123
0...300 s
V124
3...300 s
V125
0.1...300 s
V126
0.1...300 s
V127
0.1...300 s
V128
0.1...300 s
V129
0...255
V130
0...1023
V131
0...31
1MRS 755535
Default
Customer's
setting
setting
0
Default
Customer'
setting
s setting
800 Hz
0
- ABB -
00001,
I
(CT)
n
00001,
I
(CT)
n
682
0
751
50%
0
0
0
Default
Customer's
setting
setting
0.2 s
300 s
300 s
10 s
0.1 s
0.3 s
30 s
30 s
0
0
15

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents