1Mrs 755535 Ref; Variable Settings (R), Channel; Channel 2 Setting Range - ABB REF 610 Technical Reference Manual

Feeder protection relay
Hide thumbs Also See for REF 610:
Table of Contents

Advertisement

1MRS 755535
Feeder Protection Relay
Technical Reference Manual - ANSI Version
Table 4.1.17-1 Settings
Variable
Checksum, SGR 8
Checksum, SGL 1
Checksum, SGL 2
Checksum, SGL 3
Checksum, SGL 4
Checksum, SGL 5
Checksum, SGL 6
Checksum, SGL 7
Checksum, SGL 8
1)
If the protection element is out of operation, the number indicating the currently used value will be
displaced by "999" when the parameter is read via the SPA bus and by dashes on the LCD.
2)
If the optional/O module has not been installed, a dash will be shown on the LCD and "999" when the
parameter is read via the SPA bus.
3)
If the optional/O module has not been installed, a dash will be shown on the LCD and "9999999" when
the parameter is read via the SPA bus.
Auto-reclose parameters
Table 4.1.17-2 Settings
Description
CB Closing time
Pickup delay of element 51P
Pickup delay of element 51N
Reset time
Cutout time
Open time of shot 1
Open time of shot 2
Open time of shot 3
SG1
SG2
SG3
The AR function can be activated either via the HMI or with SPA parameter S25 by
setting the number of auto-reclose shots to 1, 2 or 3.
Actual
Group/
settings (R),
Channel 1
channel 0
(R, W, P)
3)
1S88
S88
S91
1S91
S92
1S92
S93
1S93
S94
1S94
S95
1S95
S96
1S96
S97
1S97
S98
1S98
Parameter
(R, W, P),
channel 0
V121
V122
V123
V124
V125
V126
V127
V128
V129
V130
V131
REF 610
Group/
Channel 2
Setting range
(R, W, P)
2S88
0...8388607
2S91
0...2097151
2S92
0...2097151
2S93
0...2097151
2S94
0...2097151
2S95
0...2097151
2S96
0...2097151
2S97
0...2097151
2S98
0...2097151
Value
0.1...10 s
0...300 s
0...300 s
3...300 s
0.1...300 s
0.1...300 s
0.1...300 s
0.1...300 s
0...255
0...1023
0...31
105