Uc" Address Duplication Of Central Remote Controller - Daikin RXYQ5-48MAY1 Service Manual

R410a heat pump 50hz
Table of Contents

Advertisement

Troubleshooting by Indication on the Remote Controller
3.49 " UC "
Address Duplication of Central Remote Controller
UC
Remote
Controller
Display
Applicable
All models of indoor unit
Models
Centralized controller
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
Supposed
Causes
Troubleshooting
240
Address duplication of centralized remote controller
Defect of indoor unit PC board
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
Optional
controllers for
centralized control are
connected to the
indoor unit.
NO
YES
Si39-407
Address duplication of central
remote controller
The setting must be changed so
that the central remote control
address is not duplicated.
Replace indoor unit PC board.
(V2828)
Troubleshooting