Daikin RXYQ5-48MAY1 Service Manual page 41

R410a heat pump 50hz
Table of Contents

Advertisement

Specifications
Ceiling Mounted Built-in Type
Model
1 Cooling Capacity (19.5°CWB)
2 Cooling Capacity (19.0°CWB)
3 Heating Capacity
Casing
Dimensions: (H×W×D)
Rows×Stages×Fin Pitch
Coil (Cross
Fin Coil)
Face Area
Model
Type
Motor Output × Number of
Units
Fan
Air Flow Rate (H/L)
4 Static external
pressure
Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Liquid Pipes
Piping
Gas Pipes
Connections
Drain Pipe
Machine Weight (Mass)
7 Sound Level (H/L) (220V)
Safety Devices
Refrigerant Control
Connectable outdoor unit
Model
Decoration
Panel Color
Panel
Dimensions: (H×W×D)
(Option)
Weight
Standard Accessories
Drawing No.
Notes:
1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level
2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level
3 Indoor temp. : 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5m, level difference:
4 Static external pressure is changeable to change over the connectors inside electrical box, this pressure
5 Static external pressure is changeable to change over the connectors inside electrical box, this pressure
6 Capacities are net, including a deduction for cooling (an additional for heating) for indoor fan motor heat.
7 Anechoic chamber conversion value, measured at a point 1.5m downward from the unit center. These
30
FXSQ20MVE
kcal/h
2,000
Btu/h
7,900
kW
2.3
kW
2.2
kcal/h
2,200
Btu/h
8,500
kW
2.5
Galvanized Steel Plate
mm
300×550×800
mm
3×14×1.75
0.088
D18H3A
Sirocco Fan
W
50×1
m³/min
9/6.5
Pa
88-39-20
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Glass Fiber
Resin Net (with Mold Resistant)
φ6.4 (Flare Connection)
mm
φ12.7 (Flare Connection)
mm
VP25
mm
(External Dia. 32 Internal Dia. 25)
kg
30
dBA
37/32
Fuse,
Thermal Protector for Fan Motor
Electronic Expansion Valve
R410A M Series
BYBS32DJW1
White (10Y9/0.5)
mm
55×650×500
kg
3
Operation Manual, Installation
Manual, Paper Pattern for Installation,
Drain Hose, Clamp Metal, Insulation
for Fitting, Sealing Pads, Clamps,
Screws, Washers.
difference: 0m.
difference: 0m.
0m. (Heat pump only)
means
"High static pressure-Standard -Low static pressure".
means
"High static pressure-Standard".
values are normally somewhat higher during actual operation as a result of ambient conditions.
FXSQ25MVE
2,500
9,900
2.9
2.8
2,800
10,900
3.2
Galvanized Steel Plate
300×550×800
3×14×1.75
0.088
D18H3A
Sirocco Fan
50×1
9/6.5
88-39-20
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Glass Fiber
Resin Net (with Mold Resistant)
φ6.4 (Flare Connection)
φ12.7 (Flare Connection)
VP25
(External Dia. 32 Internal Dia. 25)
30
37/32
Fuse,
Thermal Protector for Fan Motor
Electronic Expansion Valve
R410A M Series
BYBS32DJW1
White (10Y9/0.5)
55×650×500
3
Operation Manual, Installation
Manual, Paper Pattern for Installation,
Drain Hose, Clamp Metal, Insulation
for Fitting, Sealing Pads, Clamps,
Screws, Washers.
3D039431
Si39-407
FXSQ32MVE
3,150
12,500
3.7
3.6
3,400
13,600
4.0
Galvanized Steel Plate
300×550×800
3×14×1.75
0.088
D18H3A
Sirocco Fan
50×1
9.5/7
64-39-15
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Glass Fiber
Resin Net (with Mold Resistant)
φ6.4 (Flare Connection)
φ12.7 (Flare Connection)
VP25
(External Dia. 32 Internal Dia. 25)
30
38/32
Fuse,
Thermal Protector for Fan Motor
Electronic Expansion Valve
R410A M Series
BYBS32DJW1
White (10Y9/0.5)
55×650×500
3
Operation Manual, Installation
Manual, Paper Pattern for Installation,
Drain Hose, Clamp Metal, Insulation
for Fitting, Sealing Pads, Clamps,
Screws, Washers.
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
Specifications

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents