Daikin RXYQ5-48MAY1 Service Manual page 156

R410a heat pump 50hz
Table of Contents

Advertisement

Si39-407
c. Monitor mode
To enter the monitor mode, push the
MODE button (BS1) when in
"Setting mode 1".
<Selection of setting item>
Push the SET button (BS2) and set
the LED display to a setting item.
<Confirmation on setting contents>
Push the RETURN button (BS3) to
display different data of set items.
Push the RETURN button (BS3) and
switches to the initial status of
"Monitor mode".
∗ Push the MODE button (BS1) and
returns to "Setting mode 1".
Test Operation
No.
Setting item
Number of units for sequential
0
starting, and others
1
C/H unified address
2
Low noise/demand address
3
Not used
4
Airnet address
5
Number of connected indoor units
6
Number of connected BS units
Number of connected zone units
7
(excluding outdoor and BS unit)
8
Number of outdoor units
9
Number of connected BS units
10
Number of connected BS units
Number of zone units (excluding
11
outdoor and BS unit)
12
Number of terminal blocks
13
Number of terminal blocks
Contents of malfunction (the
14
latest)
Contents of malfunction
15
(1 cycle before)
Contents of malfunction
16
(2 cycle before)
20
Contents of retry (the latest)
21
Contents of retry (1 cycle before)
22
Contents of retry (2 cycle before)
The numbers in the "NO." column represent the number of times to press the
OPERATION (BS2) button.
Setting item 0 Display contents of "Number of units for sequential start,
and others"
(V2765)
Number of units for sequential
start
EMG operation /backup
operation setting
Defrost select setting
Te setting
Tc setting
LED display
H1P
H2P
H3P
H4P
H5P
H6P
9 7 7 7 7 7 7
9 7 7 7 7 7 8
9 7 7 7 7 8 7
9 7 7 7 7 8 8
9 7 7 7 8 7 7
9 7 7 7 8 7 8
9 7 7 7 8 8 7
9 7 7 7 8 8 8
9 7 7 8 7 7 7
9 7 7 8 7 7 8
9 7 7 8 7 8 7
9 7 7 8 7 8 8
9 7 7 8 8 7 7
9 7 7 8 8 7 8
8 7 7 8 8 8 7
8 7 7 8 8 8 8
8 7 8 7 7 7 7
8 7 8 7 8 7 7
8 7 8 7 8 7 8
8 7 8 7 8 8 7
1 unit
9 7 7 7 7 7 7
2 units
9 7 9 7 7 7 7
3 units
9 7 8 7 7 7 7
ON
9 7 7 8 7 7 7
OFF
9 7 7 7 7 7 7
Short
9 7 7 7 8 7 7
Medium
9 7 7 7 9 7 7
Long
9 7 7 7 7 7 7
H
9 7 7 7 7 8 7
M
9 7 7 7 7 9 7
L
9 7 7 7 7 7 7
H
9 7 7 7 7 7 8
M
9 7 7 7 7 7 9
L
9 7 7 7 7 7 7
Field Setting
Data display
H7P
See below
Lower 6 digits
Lower 4 digits:
upper
Lower 4 digits:
lower
Lower 6 digits
Lower 4 digits:
upper
Lower 4 digits:
lower
Malfunction
code table
Refer page
180, 181.
145

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents