Malfunction Of Transmission Between Central Remote Controller And Indoor Unit; Remote Controller And Indoor Unit - Daikin RXYQ5-48MAY1 Service Manual

R410a heat pump 50hz
Table of Contents

Advertisement

Si39-407
3.50 " UE "
Malfunction of Transmission Between Central

Remote Controller and Indoor Unit

UE
Remote
Controller
Display
Applicable
All models of indoor units
Centralized controller
Models
Method of
Microcomputer checks if transmission between indoor unit and centralized remote controller is
normal.
Malfunction
Detection
Malfunction
When transmission is not carried out normally for a certain amount of time
Decision
Conditions
Supposed
Causes
Troubleshooting
Malfunction of transmission between optional controllers for centralized control and indoor
unit
Connector for setting master controller is disconnected.
Failure of PC board for centralized remote controller
Defect of indoor unit PC board
Troubleshooting by Indication on the Remote Controller
241

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents