Uf" Refrigerant System Not Set, Incompatible Wiring/Piping - Daikin RXYQ5-48MAY1 Service Manual

R410a heat pump 50hz
Table of Contents

Advertisement

Si39-407
3.51 " UF "
Refrigerant System not Set, Incompatible Wiring/
Piping
UF
Remote
Controller
Display
Applicable
All models of indoor units
RXYQ5MA~48MA
Models
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
Supposed
Causes
Troubleshooting
Note:
Test operation may not be successful if carried out after the outdoor unit has been off for more
than 12 hours, or if it is not carried out after running all connected indoor units in the fan mode
for at least an hour.
Troubleshooting
Improper connection of transmission wiring between outdoor unit and outdoor unit outside
control adaptor
Failure to execute wiring check operation
Defect of indoor unit PC board
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
Are the stop
valves openned?
YES
Is the
test operation
(Wiring check operation)
carried out?
YES
Is
indoor - outdoor
and outdoor - outdoor unit
transmission wiring
normal?
YES
Troubleshooting by Indication on the Remote Controller
NO
Is indoor
-outdoor and outdoor-
NO
outdoor unit transmission
wiring normal?
NO
NO
Open stop valve.
YES
Replace indoor unit PC board.
After fixing incorrect wiring,
push and hold the RESET
button on the master outdoor
unit PC board for 5 seconds.
∗ The unit will not run for up to
12 minutes.
Test operation may not have
been carried out successfully.
(V2830)
243