Refrigerant Circuit
1.4

Outdoor air processing unit

1.4.1 Refrigerant System
Th2
Main Control Equipment
SH control: Superheated control of heat exchanger outlet
SC control: Subcooled control of heat exchanger outlet
Thermistor
56
Th1
A
Code
Symbol
A
Y1E
Motorized valve
B
Y1S
Solenoid valve
C
Capillary tube
Code
Symbol
Suction air temperature
Th1
R1T
thermistor
Liquid pipe temperature
Th2
R2T
thermistor
Gas pipe temperature
Th3
R3T
thermistor
Discharge air
Th4
R4T
temperature thermistor

FXMQ125MFV1~250MFV1

Th4
Th3
C
B
Name
Used to control the flow rate of refrigerant, and
make the SH control while in cooling or the SC
control while in heating.∗
Used to bypass hot gas while in heating with
thermostat OFF.
Used to reduce pressure from high to low in
bypassing hot gas.
Name
Used to turn ON or OFF the thermostat and select
cooling or heating operation.
Used to control the opening degree of EV (Y1F)
under the SC control.
Used to control the opening degree of EV (Y1E)
under the SH control.
Used to control the electric expansion valve
opening and thermostat ON/OFF so as to keep the
discharge air temperature at the set temperature.
Si39-407
4D018650B
Main function
Main function
Refirgerant Circuit