Piping Installation Point
5.
Piping Installation Point
5.1
Piping Installation Point
The projection part between multi connection piping kits
When the piping length between the multi connection kits or between multi connection kit and
outdoor unit is 2m or more, prepare a vertical projection part (200mm or more as shown below) only
on the gas pipe line location less than 2m from multi connection kit.
In the case of 2m or less
312
Less than 2m
V3037
Si39-407
Appendix