Special Control; Startup Control - Daikin RXYQ5-48MAY1 Service Manual

R410a heat pump 50hz
Table of Contents

Advertisement

Si39-407
3.

Special Control

3.1

Startup Control

This control is used to equalize the pressure in the front and back of the compressor prior to the startup of the
compressor, thus reducing startup loads. Furthermore, the inverter is turned ON to charge the capacitor.
In addition, to avoid stresses to the compressor due to oil return or else after the startup, the following control is made
and the position of the four way valve is also determined.
3.1.1 Startup Control in Cooling Operation
Compressor
Outdoor unit fan
Four way valve
Main motorized valve (EV1)
Subcooling motorized valve
(EV2)
Hot gas bypass valve
(SVP)
Receiver gas discharging
valve (SVG)
Ending conditions
3.1.2 Startup Control in Heating Operation
Compressor
Outdoor unit fan
Four way valve
Main motorized valve (EV1)
Subcooling motorized valve
(EV2)
Hot gas bypass valve
(SVP)
Receiver gas discharging
valve (SVG)
Non-operating unit liquid
pipe stop valve (SVSL)
Ending conditions
Function
Thermostat ON
Pressure equalization
control prior to startup
OFF
OFF
OFF
0 pls
0 pls
ON (140 • 160 models)
OFF (224 ~ 450 models)
OFF
140 and 160 models
• Pc - Pe<0.20MPa
OR
• A lapse of three
minutes
224 to 450 models
• A lapse of 15 seconds
Thermostat ON
Pressure equalization
control prior to startup
OFF
STEP4
ON
0 pls
0 pls
ON (140 • 160 models)
OFF (224 ~ 450 models)
OFF
ON
140 and 160 models
• Pc - Pe<0.20MPa
OR
• A lapse of three
minutes
224 to 450 models
• A lapse of 15 seconds

Startup control

STEP1
52Hz
+2 steps/20 seconds
+OFF +OFF
(until Pc - Pe>0.39MPa is achieved)
+1 step/15 seconds (when Pc>2.16MPa)
OFF
-1 step/15 seconds (when Pc<1.77MPa)
OFF
OFF
2000 pls
2000 pls
0 pls
0 pls
ON
ON
OFF
OFF
A lapse of 5
OR
seconds
Startup control
STEP1
52Hz
+2 steps/20 seconds
+OFF +OFF
(until Pc - Pe>0.39MPa is achieved)
OFF
STEP8
ON
ON
0 pls
0 pls or 180 pls
0 pls
0 pls
ON
ON
OFF
OFF
ON
ON
A lapse of 5
OR
seconds

Special Control

STEP2
• A lapse of 320 seconds
• Pc - Pe>0.39MPa
STEP2
• A lapse of 130 seconds
• Pc>2.94MPa
85