Daikin RXYQ5-48MAY1 Service Manual page 313

R410a heat pump 50hz
Table of Contents

Advertisement

List of Electrical and Functional Parts
Item
Inverter
Compressor
STD 1
STD 2
Fan motor
Electronic expansion valve (Main)
Electronic expansion valve (Subcool)
High pressure
switch
Pressure
protection
Low pressure sensor
Fusible plug
Discharge gas temperature
protection
(Discharge pipe thermistor)
Temperature
protection
Inverter fin temperature
protection
(Radiator fin thermistor)
Others
Fuse
302
Name
Symbol
Type
M1C
OC protection
device
Type
M2C
OC protection
device
Type
M3C
OC protection
device
OC protection
M1F
device
Y1E
Y2E
For M1C
S1PH
For M2C
S2PH
For M3C
S3PH
SLNPL
R3T
R1T
F1U
For main PC
board
F2U
For Noise filter
F1U
PC board
Model
RXYQ12MAY1
RXYQ14MAY1
JT1G-VDKYR@T
13.5A
JT170G-KYE@T
15.0A
1.8A
Fully closed: 0pls
Fully closed: 0pls
+0
OFF: 4.0
MPa
−0.12
+0
OFF: 4.0
MPa
−0.12
OFF: 0.07MPa
open: 70~75°C
OFF: 135°C
OFF: 98°C
250V AC 10A Class B
250V AC 10A Class B
250V AC 5A Class B
Si39-407
RXYQ16MAY1
JT170G-KYE@T
15.0A
Fully open: 2000pls
Fully open: 2000pls
ON: 3.0±0.15MPa
ON: 3.0±0.15MPa
+0
OFF: 4.0
MPa
−0.12
ON: 3.0±0.15MPa