Daikin RXYQ5-48MAY1 Service Manual page 163

R410a heat pump 50hz
Table of Contents

Advertisement

Field Setting
Address setting procedure
Adjust the Address No. (middle 2 digits) and the Pin No. (lower 3 digits) of the external control
adapter (dip switch) to those of the outdoor unit main PC board (LED), using binary numbers.
152
External control adapter
Address
Pin
No.
No.
DS2
DS1
No 0 No 0
0
No 0 No 1
0
No 0 No 2
0
No 0 No 3
0
No 1 No 4
1
No 2 No 5
2
No 3 No 6
3
No 3 No 7
3
Adjust to the same number.
Top
( ON )
(The black box represents the switch knob.)
Outdoor unit main PC board LED
Set in Setting mode 2.
Centralized Pin
83 33 333
0
0
0
83 33 338
1
0
1
83 33 383
2
0
2
83 33 388
3
0
3
83 38 833
4
1
4
83 83 838
5
2
5
83 88 883
6
3
6
83 88 888
7
3
7
Adjust to the same number.
8
ON
3
OFF
Bottom
( OFF )
Si39-407
Test Operation