■Wire end treatment
With regard to the cable end treatment, use a stranded cable or solid cable as is, or use a wire ferrule with insulating sleeve.
When using a stranded cable or solid cable as is
• Twist the end of stranded wire and make sure that there are no loose wires.
• Please do not solder plate the ends of the cable.
Dimensions of the cable end
FX5U CPU module built-in RS-485 port
5 mm
(0.2")
When using a wire ferrule with insulation sleeve
Because it is difficult to insert a cable into an insulating sleeve depending on the thickness of the cable sheath, select the
proper cable according to the outline drawing.
FX5U CPU module built-in RS-485 port
Insulating sleeve
2 to 2.5 mm
(0.07" to 0.09")
10.5 to 12 mm
(0.41" to 0.47")
<Reference>
FX5U CPU module built-in RS-485 port
FX5UC CPU module built-in RS-485 port
FX5-485-BD
FX5-485ADP
Tool
For tightening the terminal, use a commercially available small screwdriver with
straight tip that is not widened toward the end as shown below.
 Precautions
If the diameter of the screwdriver tip is too small, the required tightening torque
cannot be achieved. To achieve the appropriate tightening torque shown in the
previous page, use the following screwdriver or its equivalent (grip diameter:
approximately 25 mm (0.98")).
<Reference>
Manufacturer
Phoenix Contact
3 MC PROTOCOL
54
3.5 Wiring
Contact area
(crimp area)
6 mm
(0.23")
Manufacturer
Phoenix Contact
FX5UC CPU module built-in RS-485 port, FX5-485-BD,
FX5-485ADP
9 mm
(0.36")
FX5UC CPU module built-in RS-485 port, FX5-485-BD,
FX5-485ADP
Insulating sleeve
Contact area
(crimp area)
8 mm
(0.31")
2.6 mm
(0.1")
14 mm
(0.55")
Model name
AI 0.5-6WH
AI 0.5-8WH
0.4 mm
(0.01")
Model name
SZS 0.42.5
Crimping tool
CRIMPFOX 6
CRIMPFOX 6T-F
With straight tip
2.5 mm
(0.09")