Mitsubishi Electric FX5 User Manual page 32

Melsec iq-f series
Hide thumbs Also See for FX5:
Table of Contents

Advertisement

Data transfer
sequence error in
slave station No. 1
SM9041
Data transfer
sequence error in
slave station No. 2
SM9042
Refer to the above for creating the error monitoring program of station number 3 or later.
For details on the link devices, refer to Page 25 Contents of related devices.
For cautions on program creation, refer to Page 32 Cautions on program creation.
2 N:N NETWORK
30
2.7 Programming
M4064
M4065
Y11
M4066
M15
MOV
K4M4070
K4Y20
MOV
D1010
D10
M4128
M4129
Y12
M4130
M18
MOV
K4M4140
K4M20
MOV
D1020
D20
Program for reading link devices
(slave station → master station)
This program is required to read information from
each slave station to the master station.Monitor link
errors in each slave station, and read them.
The information from M4064 (link device) is read to
M0
M0.
The information from M4065 (link device) is read to
Y11.
The information from M4066 (link device) is read to
M15.
The information from M4070 to M4085 (link devices)
is read to Y20 to Y37.
The information from D1010 (link device) is read to
D10.
The information from M4128 (link device) is read to
M1
M1.
The information from M4129 (link device) is read to
Y12.
The information from M4130 (link device) is read to
M18.
The information from M4140 to M4155 (link devices)
is read to M20 to M35.
The information from D1020 (link device) is read to
D20.