Mitsubishi Electric FX5 User Manual page 28

Melsec iq-f series
Hide thumbs Also See for FX5:
Table of Contents

Advertisement

Link device
The devices are assigned according to the set pattern in the the refresh range setting as the following set device number (All
stations, bit device (M): 4000, word device (D): 1000) set at the head. (Page 17 Link specifications)
■Pattern 0
Station
Master
number
station
Station No.
0
Word devices
D1000
(4 points for each
to D1003
station)
■Pattern 1
Station
Master
number
station
Station No.
0
Bit devices
M4000
(32 points for each
to M4031
station)
Word devices
D1000
(4 points for each
to D1003
station)
■Pattern 2
Station
Master
number
station
Station No.
0
Bit devices
M4000
(64 points for each
to M4063
station)
Word devices
D1000
(8 points for each
to D1007
station)
Precautions
When creating a program, do not change the information in devices used by other stations. If such information is changed, the
other stations will not operate normally.
2 N:N NETWORK
26
2.7 Programming
Slave stations
Station No.
Station No.
1
2
D1010
D1020
to D1013
to D1023
Slave stations
Station No.
Station No.
1
2
M4064
M4128
to M4095
to M4159
D1010
D1020
to D1013
to D1023
Slave stations
Station No.
Station No.
1
2
M4064
M4128
to M4127
to M4191
D1010
D1020
to D1017
to D1027
Station No.
Station No.
3
4
D1030
D1040
to D1033
to D1043
Station No.
Station No.
3
4
M4192
M4256
to M4223
to M4287
D1030
D1040
to D1033
to D1043
Station No.
Station No.
3
4
M4192
M4256
to M4255
to M4319
D1030
D1040
to D1037
to D1047
Station No.
Station No.
5
6
D1050
D1060
to D1053
to D1063
Station No.
Station No.
5
6
M4320
M4384
to M4351
to M4415
D1050
D1060
to D1053
to D1063
Station No.
Station No.
5
6
M4320
M4384
to M4383
to M4447
D1050
D1060
to D1057
to D1067
Station No.
7
D1070
to D1073
Station No.
7
M4448
to M4479
D1070
to D1073
Station No.
7
M4448
to M1010
D1070
to D1077

Advertisement

Table of Contents
loading

Table of Contents