Operation error
Operation errors pertaining to the instruction are as follows.
Operation Error Flag
SM0
SM1
ON
ON
ON
ON
Program example
Reads value of the following inverter (station No. 6) parameters to storage device for PLC (CH1).
Example of program using second parameter specification code (Page 117) of FREQROL-F700P Series inverter.
Parameter No.
C2
C3
125
C4
Reading
contact
X1
Command
contact
M0
Instruction execution
completed flag
SM8029
4 INVERTER COMMUNICATION
108
4.8 Programming
Operation Error
Codes
SM56
SM8067
SD0
1810
2820
3405
3600
Name
Terminal 2 frequency setting bias
frequency
Terminal 2 frequency setting bias
Terminal 2 frequency setting gain
frequency
Terminal 2 frequency setting gain
(s1)
(s2)
IVRD
K6
K902 D100
IVRD
K6
K1902 D101
IVRD
K6
K903 D102
IVRD
K6
K1903 D103
Description
SD8067
When specified channel is used with another instruction.
When specified device exceeds the device range.
When the value specified for (s1) is other than K0 to 31.
When the value specified for (s2) is outside the range that can be specified.
(Less than K0, K3000 to 9999, K13000 to 32767)
When the value specified for (n) is other than K1 to 4.
When specified channel is not setting parameter.
Second parameter
specification code
902
1902
903
1903
SET
M0
(d1)
(n)
(d2)
Terminal 2 frequency setting bias frequency
K1
M200
→ D100
Head bit device number of instruction
execution status output
Communication channel: 1 to 4
Read value storage destination
Inverter parameter number (decimal)
Inverter station number: 0 to 31
Terminal 2 frequency setting bias
K1
M210
→ D101
The unit is specified by Analog
input selection [Pr.73].
K1
M220
Terminal 2 frequency setting gain
frequency → D102
Terminal 2 frequency setting gain
K1
M230
→ D103
The unit is specified by Analog
input selection [Pr.73].
RST
M0
Storage devices
D100
D101
D102
D103