Terminator - Mitsubishi Electric FX5 User Manual

Melsec iq-f series
Hide thumbs Also See for FX5:
Table of Contents

Advertisement

Considerations for configuring packet element
• Only one header can be used in a packet.
• A header can be set only at the head of a packet.
Header

Terminator

Use this element when a code or character string indicating the end of the packet is included.
Window
Item
Element Name
Code Type
Setting Value
Considerations for configuring packet element
• Only one terminator can be used in a packet.
• A terminator can be set only at the end of a packet. Check code and static data only can be placed after the terminator.
Header
6 PREDEFINED PROTOCOL SUPPORT FUNCTION
178
6.7 Packet Setting
Data area
Description
Set the name of the element.
Select a data type of the setting value.
• ASCII String
• ASCII Control Code
• HEX
Set data within 1 to 50 bytes.
The setting ranges that can be set for each code type are as follows:
• ASCII String
: 20H to 7EH
• ASCII Control Code: 00H to 1FH, and control code of 7FH
• HEX
: hexadecimal data of 00H to FFH
Data area
Terminator
Remarks
Setting example
• ASCII String: 'ABC'
• ASCII Control Code: ETX
• HEX: FFFF
Check code
Terminator
Static data

Advertisement

Table of Contents
loading

Table of Contents