Connecting cables
The table below shows applicable cables and tightening torques.
FX5U CPU module built-in RS-485 port
FX5UC CPU module built-in RS-485 port
FX5-485-BD
FX5-485ADP
Precautions
Do not tighten terminal screws with torque beyond the specified range. Otherwise it may cause equipment failure or
malfunction.
■Wire end treatment
With regard to the cable end treatment, use a stranded cable or solid cable as is, or use a wire ferrule with insulating sleeve.
When using a stranded cable or solid cable as is
• Twist the end of stranded wire and make sure that there are no loose wires.
• Please do not solder plate the ends of the cable.
Dimensions of the cable end
FX5U CPU module built-in RS-485 port
5 mm
(0.2")
When using a wire ferrule with insulation sleeve
Because it is difficult to insert a cable into an insulating sleeve depending on the thickness of the cable sheath, select the
proper cable according to the outline drawing.
FX5U CPU module built-in RS-485 port
Insulating sleeve
2 to 2.5 mm
(0.07" to 0.09")
10.5 to 12 mm
(0.41" to 0.47")
<Reference>
FX5U CPU module built-in RS-485 port
FX5UC CPU module built-in RS-485 port
FX5-485-BD
FX5-485ADP
5 NON-PROTOCOL COMMUNICATION
132
5.5 Wiring
Number of wires
connected per
terminal
One wire
Two wires
One wire
Two wires
Contact area
(crimp area)
6 mm
(0.23")
Manufacturer
Phoenix Contact
Wire size
Solid wire,
Wire ferrule with
Stranded wire
insulation sleeve
2
0.2 to 0.5 mm
0.2 to 0.5 mm
(AWG24 to 20)
(AWG24 to 20)
2
0.2 mm
(AWG24)
2
0.3 to 0.5 mm
0.3 to 0.5 mm
(AWG22 to 20)
(AWG22 to 20)
2
0.3 mm
(AWG22)
FX5UC CPU module built-in RS-485 port, FX5-485-BD,
FX5-485ADP
9 mm
(0.36")
FX5UC CPU module built-in RS-485 port, FX5-485-BD,
FX5-485ADP
Contact area
Insulating sleeve
(crimp area)
8 mm
(0.31")
2.6 mm
(0.1")
14 mm
(0.55")
Model name
AI 0.5-6WH
AI 0.5-8WH
Tightening torque
2
0.22 to 0.25 Nm
2
Crimping tool
CRIMPFOX 6
CRIMPFOX 6T-F